Plan Review Notes For Permit 18040798 |
Permit Number |
18040798 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-05 16:59:36 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. WHAT TYPE OF WATER IS DISCHARGING TO THE PITS AND | | WHAT TYPE WILL DISCHARGE TO THE FLOOR DRAIN IN SHED THE | | FOLLOWING SHALL NOT DISCHARGE TO THE SANITARY SYSTEM | | STORM WATER, POOL OR FOUNTAIN WATER, WELL WATER OR ANY | | UNTREATED WATER PER WEST PALM BEACH, FLORIDA - CODE OF | | ORDINANCES | | / CHAPTER 90 - UTILITIES | | / ARTICLE III. - SEWERS AND SEWAGE DISPOSAL | | SEC. 90-126. - PROHIBITIONS AND LIMITATIONS OF | | DISCHARGE.(5) | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|