2018-05-14 16:10:21 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18040798 | | 5/14/18 | | | | CODES IN EFFECT: | | FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW | | AC SYSTEM- SECTION C403.2.1 FBC-EC. | | | | 2) SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE NEW | | CONDITIONED BUILDING ADDITION- SECTION C101.3 & | | C101.5.1 FBC-EC. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | PLAN REVIEW RESULTS: DENIED. | | |
|