Plan Review Notes For Permit 18040798 |
Permit Number |
18040798 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-05-22 07:14:49 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. REVISE PLAN TO INCLUDE THE FOLLOWING INFORMATION: | | | | FBC B TABLE 504.4, TABLE 506.2 (BUILDING HEIGHT AND | | AREA) | | FBC B CHAPTER 6, BUILDING TYPE | | FBC B TABLE 602, FIRE RESISTANCE RATING REQUIREMENTS | | FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE | | FBC B 705.3, BUILDINGS ON THE SAME LOT, SHOW DISTANCE | | FROM PROPOSED SHED TO ASSUMED PROPERTY LINE (DISTANCE | | FROM EX. RESIDENCE #325 TO ASSUMED PROPERTY LINE, | | DISTANCE FROM PROPOSED STORAGE SHED TO ASSUMED PROPERTY | | LINE, SHOW COMPLIANCE FOR BOTH STRUCTURES) | | FBC B 1603.1.4, WIND DESIGN CRITERIA | | FBC 107, GOVERNING CODE | | |
|