Plan Review Notes
Plan Review Notes For Permit 18040797
Permit Number 18040797
Review Stop E
Sequence Number 2
Notes
Date Text
2018-06-29 15:35:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE GRAPH/CALCULATION OF EXTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CONSERVATION IN RELATION
 TO THE CONNECTED EXTERIOR LIGHTING PROPOSED TO COMPLY
 WITH CODE. FBC EC C405.5.1 (COMMENT RESPONSE STATES
 THAT THIS CODE REFERS TO INTERIOR LIGHTING. I'M NOT
 SURE WHICH YEAR CODE YOU ARE LOOKING AT, BUT IN THE
 2017 FBC ENERGY CONSERVATION, THIS SECTION IS FOR
 EXTERIOR LIGHTING. IT APPEARS THAT YOU ARE REQUESTING
 EXEMPTION THAT IS USED FOR THEME ELEMENTS IN
 AMUSEMENT/THEME PARKS, WHICH DOES NOT APPLY TO THIS
 SUBMITTAL. PROVIDE AS PREVIOUSLY REQUESTED. YOU ARE
 WELCOME TO DISCUSS THIS WITH THE BUILDING OFFICIAL IF
 YOU DISAGREE.)
 2. WILL CAMERAS HAVE HIGH VOLTAGE WIRING IN ADDITION TO
 LOW VOLTAGE WIRING? PROVIDE CLARIFICATION. FBC 107.2.1
 (BASED ON COMMENT RESPONSE, PROVIDE DETAIL OF
 SEPARATION FOR LOW VOLTAGE WIRING FROM POWER WIRING.
 NEC 725.136)
 3. CORRECTED.
 4. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  