2018-04-24 13:19:43 | 04/24/2018 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THERE IS AN EXISTING RESTROOM, PERMIT 18010296, ON |
| THIS PROPERTY. IS THIS THE RESTROOM THAT WAS FINISHED |
| AND PLAN THAT WAS SUBMITTED, IS IT BEING CHANGED OR IS |
| IT A NEW RESTROOM? PLEASE CLARIFY THIS. 2017 FBC ACC |
| CODE 604.3 CLEARANCE. |
| 2. IF IT IS A NEW RESTROOM SHOW THAT IT COMPLIES WITH |
| FBC ACCEPTABILITY, PLEASE SHOW CLEAR FLOOR SPACE AND |
| DIMENSION REFLECT THE LOCATION OF FIXTURES DETAIL OF |
| HEIGHTS AND DIMENSION NOT SHOWN, PLEASE PROVIDE DETAIL |
| DRAWINGS PER 2017 FBC ACCESSIBILITY CODE. |
| 3. PROVIDE MINIMUM SANITARY FACILITIES ACCORDING TO |
| 2017 FBC P TABLE 403.1. |
| 4. VENTING OF PLUMBING RISER DIAGRAM REQUIRED WPB |
| AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL |
| PLUMBING |
| 5. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED |
| CONTRACT. WPB AMENDMENTS TO THE FBC SEC. 109.3 BUILDING |
| PERMIT VALUATIONS. |
| 6. IS THIS FLOOR BEING CUT AND PIPES BEING MOVED, |
| SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE WIDTH |
| OF THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO |
| BE REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE |
| AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH |
| INTO THE EXISTING SLAB, AND THE SPACING OF THE DOWELS |
| ON CENTER. THE REPAIR SHALL ALSO INCLUDE TERMITE |
| TREATMENT OF THE SOIL AND THE REQUIRED VAPOR BARRIER |
| OVER THE SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL |
| BE ONSITE FOR FINAL INSPECTION. |
| 7. THIS LOCATION HAS BEEN CITED FOR WORK BEING DONE |
| WITHOUT A PERMIT AND INSPECTION SO IT APPEARS THAT |
| THERE IS THE OTHER TRADE THAT REQUIRES A PERMIT |
| APPLICATION, ELECTRICAL, MECHANICAL AND DRYWALL |
| FRAMING. FBC WPB A 105.1 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |