Plan Review Notes
Plan Review Notes For Permit 18040714
Permit Number 18040714
Review Stop P
Sequence Number 1
Notes
Date Text
2018-04-24 13:19:4304/24/2018 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THERE IS AN EXISTING RESTROOM, PERMIT 18010296, ON
 THIS PROPERTY. IS THIS THE RESTROOM THAT WAS FINISHED
 AND PLAN THAT WAS SUBMITTED, IS IT BEING CHANGED OR IS
 IT A NEW RESTROOM? PLEASE CLARIFY THIS. 2017 FBC ACC
 CODE 604.3 CLEARANCE.
 2. IF IT IS A NEW RESTROOM SHOW THAT IT COMPLIES WITH
 FBC ACCEPTABILITY, PLEASE SHOW CLEAR FLOOR SPACE AND
 DIMENSION REFLECT THE LOCATION OF FIXTURES DETAIL OF
 HEIGHTS AND DIMENSION NOT SHOWN, PLEASE PROVIDE DETAIL
 DRAWINGS PER 2017 FBC ACCESSIBILITY CODE.
 3. PROVIDE MINIMUM SANITARY FACILITIES ACCORDING TO
 2017 FBC P TABLE 403.1.
 4. VENTING OF PLUMBING RISER DIAGRAM REQUIRED WPB
 AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL
 PLUMBING
 5. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT. WPB AMENDMENTS TO THE FBC SEC. 109.3 BUILDING
 PERMIT VALUATIONS.
 6. IS THIS FLOOR BEING CUT AND PIPES BEING MOVED,
 SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE WIDTH
 OF THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO
 BE REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE
 AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH
 INTO THE EXISTING SLAB, AND THE SPACING OF THE DOWELS
 ON CENTER. THE REPAIR SHALL ALSO INCLUDE TERMITE
 TREATMENT OF THE SOIL AND THE REQUIRED VAPOR BARRIER
 OVER THE SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL
 BE ONSITE FOR FINAL INSPECTION.
 7. THIS LOCATION HAS BEEN CITED FOR WORK BEING DONE
 WITHOUT A PERMIT AND INSPECTION SO IT APPEARS THAT
 THERE IS THE OTHER TRADE THAT REQUIRES A PERMIT
 APPLICATION, ELECTRICAL, MECHANICAL AND DRYWALL
 FRAMING. FBC WPB A 105.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  