2018-04-23 10:54:00PERMIT # 18040713
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE USE OF
 THE FLEXIBLE SPRINKLER DROPS AND THE ADDITIONAL
 FRICTION LOSS ASSOCIATED WITH THESE PRODUCTS.
  
 2) PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE
 MAXIMUM NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND
 RADIUS PERMITTED IN THE LISTING DATA.
  
 3) INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROP TO BE
 USED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  