Plan Review Notes For Permit 18040713 |
Permit Number |
18040713 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-04-23 10:54:00 | PERMIT # 18040713 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FAILED COMMENTS: | | | | 1) PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE USE OF | | THE FLEXIBLE SPRINKLER DROPS AND THE ADDITIONAL | | FRICTION LOSS ASSOCIATED WITH THESE PRODUCTS. | | | | 2) PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE | | MAXIMUM NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND | | RADIUS PERMITTED IN THE LISTING DATA. | | | | 3) INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROP TO BE | | USED. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | [email protected] | | |
|