Plan Review Notes
Plan Review Notes For Permit 18040706
Permit Number 18040706
Review Stop G
Sequence Number 1
Notes
Date Text
2018-04-25 07:00:441) CITY RECORDS SHOW A PREVIOUS GAS PERMIT FOR THIS
 ADDRESS. THE PLANS INDICATE AN EXISTING GAS METER. THE
 BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO
 THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 ***NOTE: I HAVE INCLUDED A COPY OF THE EXISTING GAS
 PLAN FOR YOUR USE TO REVISE YOUR GAS DRAWING.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  