Plan Review Notes For Permit 18040706 |
Permit Number |
18040706 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-04-25 07:00:44 | 1) CITY RECORDS SHOW A PREVIOUS GAS PERMIT FOR THIS | | ADDRESS. THE PLANS INDICATE AN EXISTING GAS METER. THE | | BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO | | THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING | | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING | | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING | | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS | | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH | | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH | | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF | | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. | | | | ***NOTE: I HAVE INCLUDED A COPY OF THE EXISTING GAS | | PLAN FOR YOUR USE TO REVISE YOUR GAS DRAWING. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | | | |
|