2018-06-02 03:11:26 | 1) INDICATE ON THE GAS PLANS THE TYPE OF PIPE MATERIAL |
| BEING INSTALLED FOR THE GAS LINE. |
| 2) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| G2413.1, G2413.2, & G2413.3. |
| 4) SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION, |
| SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND |
| ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL |
| GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426 |
| THROUGH G2439. |
| 5) SHOW THE SQUARE INCH AREA OF BOTH LOUVERS ON THE |
| ENCLOSURE. ATHE NET FREE AREA OF METAL LOUVERS SHALL BE |
| ASSUMED TO 75 PERCENT OF THE SQUARE INCH AREA OF THE |
| LOUVER PER THE 2017 FBC-FUEL GAS SEC. 304.10. |
| 6) COMBUSTION AIR REQUIREMENTS SHALL COMPLY WITH 2017 |
| FBC-FUEL GAS SEC.304.6. |
| 7) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE WATER HEATER.THE HOUSE PLAN CAN BE HAND |
| DRAWN.WPB AMEND TO FBC SEC. 107.2.1. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| |
| |
| |
| |
| |