Plan Review Notes
Plan Review Notes For Permit 18040690
Permit Number 18040690
Review Stop B
Sequence Number 2
Notes
Date Text
2018-05-30 17:45:09PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC EXISTING BUILDING SECTION 606.1
  
 4) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED ARE FOR
 EXPOSURE CATEGORY B. THIS PROJECT IS LOCATED ON CLEAR
 LAKE AND IS EXPOSURE C. THE STRUCTURAL PLANS THAT HAVE
 BEEN SIGNED AND SEALED BY MICHEAL A. GIOVANNOZZI, P.E.
 SPECIFY THE EXPOSURE AS C. SUBMIT RAS 117 CALCULATIONS
 THAT ARE FOR EXPOSURE C. LIMITATION NUMBER 7 ON PAGE 16
 OF THE ROOFING PRODUCT ( NOA NO. 13-0204.14 ) REQUIRES
 THE RAS 117 CALCULATIONS TO BE SIGNED AND SEALED. FAC
 61G15-23.001 REQUIRES A FLORIDA LICENSED PROFESSIONAL
 ENGINEER TO SIGN AND SEAL ALL OF THEIR DOCUMENTS THAT
 ARE SUBMITTED FOR PUBLIC RECORD. FS 471.025
  
 5) THE WATER HEATER ENCLOSURE THAT WAS SUBMITTED DOES
 NOT HAVE PRODUCT APPROVALS AND HAS NOT BEEN TESTED FOR
 WINDLOADS. SUBMIT PRODUCT APPROVALS FOR A WATER HEATER
 ENCLOSURE THAT MEETS THE REQUIRED WINDLOADS. FBC
 107.3.4 THE PLANS INDICATE THAT THE EXISTING GAS WATER
 HEATER IS TO BE MOVED TO THE EXTERIOR OF THE STRUCTURE.
 PROVIDE ADDITIONAL INFORMATION SUCH AS IS IT A TANKLESS
 WATER HEATER LABELED FOR OUTDOOR INSTALLATION OR ONE
 WITH A TANK THAT REQUIRES IT TO BE INSIDE OF A
 STRUCTURE. IF A STRUCTURE IS REQUIRED TO PROTECT IT
 FROM THE ELEMENTS PROVIDE DETAILS. FBC 107.2.1 AND
 FBCR-P2801.3
  
  
  
  
  
  
  
  