Plan Review Notes For Permit 18040690
Permit Number 18040690
Review Stop B
Sequence Number 1
Notes
Date Text
2018-04-18 11:39:36PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEER'S PLANS REFERENCE THE FBC FIFTH EDITION
 (2014). THE FBC SIXTH EDITION (2017) WENT INTO EFFECT
 ON JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR ON OR
 AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC SIXTH EDITION (2017). FS CHAPTER 553
  
 2) THE WIND DESIGN DATA IS NOT SPECIFIED ON THE
 ENGINEER'S DRAWINGS. FBC EXISTING BUILDING SECTION
 606.1
  
 3) THE ENGINEER SHALL SPECIFY THE REQUIRED DESIGN
 UPLIFT , GRAVITY AND LATERAL LOADS FOR THE NEW
 STRUCTURAL BEAMS ON THE SIGNED AND SEALED PLANS. THE
 EXISTING CONNECTORS WILL HAVE TO BE EVALUATED BY THE
 ENGINEER TO DETERMINE IF THEY ARE ADEQUATE OR NEED TO
 BE REPLACED. SPECIFY ANY NEW CONNECTORS ON THE PLANS.
 FBC EXISTING BUILDING SECTION 606.1
  
 4) LIMITATION NUMBER 7 ON PAGE 16 OF THE ROOFING
 PRODUCT ( NOA NO. 13-0204.14 ) REQUIRES THE RAS 117
 CALCULATIONS TO BE SIGNED AND SEALED. FAC 61G15-23.001
 REQUIRES A FLORIDA LICENSED PROFESSIONAL ENGINEER TO
 SIGN AND SEAL ALL OF THEIR DOCUMENTS THAT ARE SUBMITTED
 FOR PUBLIC RECORD. FS 471.025
  
 5) THE PLANS INDICATE THAT THE EXISTING GAS WATER
 HEATER IS TO BE MOVED TO THE EXTERIOR OF THE STRUCTURE.
 PROVIDE ADDITIONAL INFORMATION SUCH AS IS IT A TANKLESS
 WATER HEATER LABELED FOR OUTDOOR INSTALLATION OR ONE
 WITH A TANK THAT REQUIRES IT TO BE INSIDE OF A
 STRUCTURE. IF A STRUCTURE IS REQUIRED TO PROTECT IT
 FROM THE ELEMENTS PROVIDE DETAILS. FBC 107.2.1 AND
 FBCR-P2801.3
  
  
  
  
  
  
  
  