2018-05-15 13:49:28 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NOTE ON PLAN STATES THAT THE "EXISTING ELECTRICAL |
| COMPLIES WITH FBC 708.3.1 NO CHANGES TO ELECTRIC ARE |
| PROPOSED OR REQUIRED." THIS CODE SECTION DOES NOT EXIST |
| IN THE FBC. PROVIDE CLARIFICATION. ALSO, UNDER |
| "ENGINEERING NOTES", IT IS INDICATED THAT THE FBC |
| RESIDENTIAL WAS USED FOR DESIGN. THE RESIDENTIAL |
| EDITION DOES NOT APPLY TO MULTI-FAMILY DWELLING. |
| PROVIDE CORRECTION. FBC RE R101.2; WPB FBC 107.2.1 |
| 2. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B) |
| 3. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| PROVIDE CORRECTION. NEC 210.52(E)(2) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |