Plan Review Notes For Permit 18040509 |
Permit Number |
18040509 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-06-06 16:04:55 | 2ND REVIEW: FBC 2017 6TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. ON THE RISER PLEASE SHOW EACH CUT SECTION OF PIPE, | | THE RISER YOU PROVIDED DOES NOT SHOW THE DROP SECTIONS | | OF PIPE DOWN FROM THE ATTIC TO THE APPLIANCE OR METER. | | SHOW THE LENGTH OF EACH CUT SECTION. WHEN I SCALED THE | | DISTANCE FROM THE METER TO THE RANGE IT WAS ABOUT 40' | | EACH DROP SECTION WOULD ADD 8'-10' TO YOUR OVERALL | | DISTANCE FROM THE METER TO THE FURTHEST APPLIANCE. THIS | | IS REQUIRED TO DETERMINE SIZE OF THE PIPING. PER | | FBC-RES SEC. G2413.4.1, G2413.4.2. | | | | 2. PROVIDE SIZING TABLE USED, YOU LISTED LESS THAN 2PSI | | WITH A 1PSI PRESSURE DROP I COULD NOT FIND A TABLE IN | | THE FUEL GAS CODE TO MATCH UP TO THESE PRESSURES. PER | | FBC-RES SEC. G2413.4.1, G2413.4.2. | | | | 3. SHOW BTU LOAD OF THE RANGE ON THE RISER. PER WPB | | AMEND TO FBC 107.2.1 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|