Plan Review Notes
Plan Review Notes For Permit 18040509
Permit Number 18040509
Review Stop G
Sequence Number 2
Notes
Date Text
2018-06-06 16:04:552ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. ON THE RISER PLEASE SHOW EACH CUT SECTION OF PIPE,
 THE RISER YOU PROVIDED DOES NOT SHOW THE DROP SECTIONS
 OF PIPE DOWN FROM THE ATTIC TO THE APPLIANCE OR METER.
 SHOW THE LENGTH OF EACH CUT SECTION. WHEN I SCALED THE
 DISTANCE FROM THE METER TO THE RANGE IT WAS ABOUT 40'
 EACH DROP SECTION WOULD ADD 8'-10' TO YOUR OVERALL
 DISTANCE FROM THE METER TO THE FURTHEST APPLIANCE. THIS
 IS REQUIRED TO DETERMINE SIZE OF THE PIPING. PER
 FBC-RES SEC. G2413.4.1, G2413.4.2.
  
 2. PROVIDE SIZING TABLE USED, YOU LISTED LESS THAN 2PSI
 WITH A 1PSI PRESSURE DROP I COULD NOT FIND A TABLE IN
 THE FUEL GAS CODE TO MATCH UP TO THESE PRESSURES. PER
 FBC-RES SEC. G2413.4.1, G2413.4.2.
  
 3. SHOW BTU LOAD OF THE RANGE ON THE RISER. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  