2018-04-30 16:40:38 | 04/30/18 DENIED BY PLUMBING |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| 1. PLUMBING RISER DIAGRAM NEEDS VENTS FOR LAUNDRY TRAY, |
| GUESS BATH AND MASTER NEED TO BE VENTED CORRECTLY, 2017 |
| FBC R3004, R3005, |
| 2. PLEASE PROVIDE WATER SUPPLY AND DISTRIBUTION SYSTEM |
| DESIGN FOR WATER RISER DIAGRAM, WPB AMENDMENTS TO THE |
| FBC SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING |
| 3. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE) |
| ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.001, FLORIDA STATUTE 471. |
| 4. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND |
| SEALED BY A LICENSED ENGINEER OR ARCHITECT. PROVIDE |
| CORRECTION. FS 471.003(2)(H); 471.025; FBC 107.2.1, |
| 107.3.5 |
| 5. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A |
| WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS |
| OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN |
| ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB |
| AND WHIRLPOOL BATHTUB VALVES. |
| 6. ON THE ROOM LABELLED POWER AND MASTER THE SHOWER PAN |
| IS NOT RECEDED IT WILL REQUIRE LINING, 2017 FBC R |
| 2709.2 |
| 7. SHOWER MEASUREMENT IN POWER IS AT 30? PLUS 4? FOR |
| CURB WHICH IS NOT SHOWN AND WATER CLOSET SHALL NOT BE |
| SET CLOSER THAN 15? INCHES FROM ITS CENTER TO ANY SIDE |
| WALL, PARTITION, VANITY OR OTHER OBSTRUCTION, OR CLOSER |
| THAN 30? INCHES CENTER TO CENTER BETWEEN ADJACENT |
| FIXTURES. THE SHOWER MAY BE SMALLER AS LONG AS IT |
| COMPLIES WITH A SHOWER COMPARTMENT THAT IS NOT LESS |
| THAN 900 SQUARE INCHES, PLEASE PROVIDE SHOWER DRAIN |
| DETAILS AND COMPLIANCE. WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |