Plan Review Notes
Plan Review Notes For Permit 18040509
Permit Number 18040509
Review Stop P
Sequence Number 1
Notes
Date Text
2018-04-30 16:40:3804/30/18 DENIED BY PLUMBING
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 1. PLUMBING RISER DIAGRAM NEEDS VENTS FOR LAUNDRY TRAY,
 GUESS BATH AND MASTER NEED TO BE VENTED CORRECTLY, 2017
 FBC R3004, R3005,
 2. PLEASE PROVIDE WATER SUPPLY AND DISTRIBUTION SYSTEM
 DESIGN FOR WATER RISER DIAGRAM, WPB AMENDMENTS TO THE
 FBC SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING
 3. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE)
 ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471.
 4. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND
 SEALED BY A LICENSED ENGINEER OR ARCHITECT. PROVIDE
 CORRECTION. FS 471.003(2)(H); 471.025; FBC 107.2.1,
 107.3.5
 5. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB
 AND WHIRLPOOL BATHTUB VALVES.
 6. ON THE ROOM LABELLED POWER AND MASTER THE SHOWER PAN
 IS NOT RECEDED IT WILL REQUIRE LINING, 2017 FBC R
 2709.2
 7. SHOWER MEASUREMENT IN POWER IS AT 30? PLUS 4? FOR
 CURB WHICH IS NOT SHOWN AND WATER CLOSET SHALL NOT BE
 SET CLOSER THAN 15? INCHES FROM ITS CENTER TO ANY SIDE
 WALL, PARTITION, VANITY OR OTHER OBSTRUCTION, OR CLOSER
 THAN 30? INCHES CENTER TO CENTER BETWEEN ADJACENT
 FIXTURES. THE SHOWER MAY BE SMALLER AS LONG AS IT
 COMPLIES WITH A SHOWER COMPARTMENT THAT IS NOT LESS
 THAN 900 SQUARE INCHES, PLEASE PROVIDE SHOWER DRAIN
 DETAILS AND COMPLIANCE. WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  