2018-04-30 16:45:27 | 04/30/18 DENIED GAS BY PLUMBING |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| 1. THE LOCATION OF THE TANKLESS WATER HEATER AND THE |
| LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS |
| IN RELATION TO THE WATER HEATER COULD NOT BE VERIFIED |
| AS INSTALLATION MANUAL IS NOT AVAILABLE. THE LOCATION |
| OF THE WATER HEATER SHALL COMPLY WITH THE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| 2. PLEASE PROVIDE INSTALLATION MANUAL FOR TANKLESS |
| WATER HEATER, SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR |
| 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| 3. PLEASE SPECIFICATION FOR ALL ALLIANCES AND LABELING, |
| GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL |
| GAS SEC. 402.2 AND 301.3 OR 2017 FBC FUEL GAS RES. SEC. |
| G2413.2 AND G2404.3. |
| 4. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC |
| FUEL GAS RES. SEC. G2421.1. |
| 5. A SEPARATE GAS PERMIT AND PLANS WILL BE REQUIRED FOR |
| A CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE |
| COMPLETE PLANS AND GAS RISER THAT REFLECTS THE ENTIRE |
| SCOPE OF GAS WORK TO BE DONE. WPB AMENDMENTS TO FBC |
| SEC. 107.2.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| [email protected] |
| 561-805-6720 |
| |