2018-05-01 09:04:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 2. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 3. GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN
 GARAGE, INCLUDING GARAGE DOOR OPENER. PROVIDE
 CORRECTION. NEC 210.8; FBC RE E3902.2
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 5. PROVIDE ACCURATE LOAD CALCULATION FOR A DWELLING
 UNIT USING FORMAT IN THE FBC RESIDENTIAL. NEC 220; FBC
 RE E3602.2
 6. RISER DIAGRAM IS NOT CODE COMPLIANT. THE SERVICE
 CONDUCTORS MUST HAVE OVERCURRENT PROTECTION AND THE
 PANEL IS SHOWN AS MAIN LUG ONLY IN PANEL SCHEDULE.
 SERVICE CONDUCTORS ARE NOT PERMITTED TO EXTEND FURTHER
 THAN 8 FEET INTO A STRUCTURE WITHOUT OVERCURRENT
 PROTECTION. IF THIS OVERCURRENT PROTECTION IS LOCATED
 ON THE EXTERIOR OF THE DWELLING, THAN THE CONDUIT TO
 THE INTERIOR PANEL MUST INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR. IF THE CONDUCTORS ARE RUN UNDERGROUND FROM
 THE METER TO THE INTERIOR PANEL, AND THAT PANEL HAS A
 MAIN BREAKER, THE CONDUCTORS MUST NOT EXCEED 8 FEET IN
 LENGTH BEFORE TERMINATION TO THE MAIN BREAKER. PROVIDE
 CORRECTION. NEC 230.70, 250.122; FBC RE E601.6,
 E3704.6, 3607.3.1
 7. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. A NOTE WILL SUFFICE. NEC 210.12; FBC RE
 E3902.16
 8. CIRCUIT 18 IN PANEL SCHEDULE SHOWS #14 WIRE ON A 20
 AMP BREAKER FOR THE BATH GFCI CIRCUIT. THE #14 WIRE IS
 NOT RATED FOR 20 AMPS. PROVIDE CORRECTION. NEC
 240.4(D); FBC RE E3705.5.3
 9. CIRCUIT 1,3 IN PANEL SCHEDULE SHOWS #10 WIRE ON A 30
 AMP BREAKER FOR THE AHU WITH 10KW HEAT. THE #10 WIRE IS
 NOT RATED TO HANDLE THIS LOAD. THE BREAKER IS NOT SIZED
 PROPERLY. PROVIDE CORRECTION. NEC 310.15(B)(16); FBC RE
 E3705.1
 10. CIRCUIT 6,8 IN PANEL SCHEDULE SHOWS #10 WIRE ON A
 30 AMP BREAKER FOR THE RANGE WITH A 8.2KW LOAD. THE #10
 WIRE IS NOT RATED TO HANDLE THIS LOAD. THE BREAKER IS
 NOT SIZED PROPERLY. PROVIDE CORRECTION. NEC
 310.15(B)(16); FBC RE E3705.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  