2018-05-01 09:04:46 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 2. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| 3. GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN |
| GARAGE, INCLUDING GARAGE DOOR OPENER. PROVIDE |
| CORRECTION. NEC 210.8; FBC RE E3902.2 |
| 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 5. PROVIDE ACCURATE LOAD CALCULATION FOR A DWELLING |
| UNIT USING FORMAT IN THE FBC RESIDENTIAL. NEC 220; FBC |
| RE E3602.2 |
| 6. RISER DIAGRAM IS NOT CODE COMPLIANT. THE SERVICE |
| CONDUCTORS MUST HAVE OVERCURRENT PROTECTION AND THE |
| PANEL IS SHOWN AS MAIN LUG ONLY IN PANEL SCHEDULE. |
| SERVICE CONDUCTORS ARE NOT PERMITTED TO EXTEND FURTHER |
| THAN 8 FEET INTO A STRUCTURE WITHOUT OVERCURRENT |
| PROTECTION. IF THIS OVERCURRENT PROTECTION IS LOCATED |
| ON THE EXTERIOR OF THE DWELLING, THAN THE CONDUIT TO |
| THE INTERIOR PANEL MUST INCLUDE AN EQUIPMENT GROUNDING |
| CONDUCTOR. IF THE CONDUCTORS ARE RUN UNDERGROUND FROM |
| THE METER TO THE INTERIOR PANEL, AND THAT PANEL HAS A |
| MAIN BREAKER, THE CONDUCTORS MUST NOT EXCEED 8 FEET IN |
| LENGTH BEFORE TERMINATION TO THE MAIN BREAKER. PROVIDE |
| CORRECTION. NEC 230.70, 250.122; FBC RE E601.6, |
| E3704.6, 3607.3.1 |
| 7. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE |
| CORRECTION. A NOTE WILL SUFFICE. NEC 210.12; FBC RE |
| E3902.16 |
| 8. CIRCUIT 18 IN PANEL SCHEDULE SHOWS #14 WIRE ON A 20 |
| AMP BREAKER FOR THE BATH GFCI CIRCUIT. THE #14 WIRE IS |
| NOT RATED FOR 20 AMPS. PROVIDE CORRECTION. NEC |
| 240.4(D); FBC RE E3705.5.3 |
| 9. CIRCUIT 1,3 IN PANEL SCHEDULE SHOWS #10 WIRE ON A 30 |
| AMP BREAKER FOR THE AHU WITH 10KW HEAT. THE #10 WIRE IS |
| NOT RATED TO HANDLE THIS LOAD. THE BREAKER IS NOT SIZED |
| PROPERLY. PROVIDE CORRECTION. NEC 310.15(B)(16); FBC RE |
| E3705.1 |
| 10. CIRCUIT 6,8 IN PANEL SCHEDULE SHOWS #10 WIRE ON A |
| 30 AMP BREAKER FOR THE RANGE WITH A 8.2KW LOAD. THE #10 |
| WIRE IS NOT RATED TO HANDLE THIS LOAD. THE BREAKER IS |
| NOT SIZED PROPERLY. PROVIDE CORRECTION. NEC |
| 310.15(B)(16); FBC RE E3705.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |