Plan Review Notes
Plan Review Notes For Permit 18040509
Permit Number 18040509
Review Stop B
Sequence Number 1
Notes
Date Text
2018-05-02 17:07:151ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
  
 18040509 - 816 SUNSET RD
  
 1) PLEASE PROVIDE A SOIL TEST PER FBC 401.4
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 2) THE SITE PLAN HAS LIMITED INFORMATION RELATIVE TO
 DRAINAGE. PLEASE PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN PER FBC-110.9 IMPACT OF CONSTRUCTION. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 NOTE PER R401.1 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152
 MM) WITHIN THE FIRST 10 FEET (3048 MM).
  
 3) PLEASE NOTE A DRIVEWAY APPROACH DETAIL IS PROVIDED.
 A SEPARATE PERMIT AND DESIGN IS REQUIRED FOR THE
 DRIVEWAY PERMIT, IT IS NOT INCLUDED IN THIS REVIEW.
 PLEASE ACKNOWLEDGE THIS IN YOUR RESPONSE TO THESE
 COMMENTS; ALSO SEE ZONING COMMENTS THAT MAY APPLY.
  
 4) PLEASE NOTE A LANDSCAPE PLAN IS PROVIDED. A SEPARATE
 PERMIT AND DESIGN IS REQUIRED FOR THE LANDSCAPE PERMIT,
 IT IS NOT INCLUDED IN THIS REVIEW. PLEASE ACKNOWLEDGE
 THIS IN YOUR RESPONSE TO THESE COMMENTS; ALSO SEE
 ZONING COMMENTS THAT MAY APPLY.
  
 5) PERMIT VALUATION ? THE CALCULATED VALUE OF THE
 IMPROVEMENT IS $271,520.00 PER THE ICC-BVD PUBLISHED
 FEBRUARY 2018 AND ADOPTED FOR USE BY CITY RESOLUTION
 367-09. THIS COVERS THE DWELLING ONLY AND NO OTHER
 SEPARATELY REQUIRED PERMITS. VALUE AND FEES DUE ARE
 ADJUSTED TO THIS FIGURE. PLEASE REFERENCE FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 6) SHEETS A-1, A-2, S-1, & S-2 CONTAIN REFERENCES TO
 THE FBC 2014 FIFTH EDITION ? PLEASE CORRECT TO THE FBC
 2017 6TH EDITION RESIDENTIAL. PLEASE NOTE SHEET A-3
 CONTAINS DESIGN PRESSURE INFORMATION AND SHOULD
 ACCORDINGLY BE SIGNED AND SEALED BY THE ENGINEER OF
 RECORD.
  
 7) THE WALL SECTION ON SHEET A-2 INDICATES THE USE OF
 ASPHALT SHINGLES AS A ROOF COVERING IN CONFLICT WITH
 THE NOTES ON SHEET A-4 AND THE PRODUCT INFORMATION
 PROVIDED WHICH INDICATE THE USE OF A SPANISH S TILE.
 PLEASE CLARIFY.
  
 8) SHEET A-1 ? NO BATHROOM DOOR MEETS THE 29? MINIMUM
 WIDTH REQUIREMENT: FBCR-320.1.1 - ALL NEW SINGLE-FAMILY
 HOUSES, DUPLEXES, TRIPLEXES, CONDOMINIUMS AND
 TOWNHOUSES SHALL PROVIDE AT LEAST ONE BATHROOM, LOCATED
 WITH MAXIMUM POSSIBLE PRIVACY, WHERE BATHROOMS ARE
 PROVIDED ON HABITABLE GRADE LEVELS, WITH A DOOR THAT
 HAS A 29-INCH (737 MM) CLEAR OPENING. HOWEVER, IF ONLY
 A TOILET ROOM IS PROVIDED AT GRADE LEVEL, SUCH TOILET
 ROOMS SHALL HAVE A CLEAR OPENING OF NOT LESS THAN 29
 INCHES (737 MM).
  
 9) SHEET A-1 CONTAINS A NOTE RELATIVE TO BEDROOM EGRESS
 WINDOW SQUARE FOOTAGE. PLEASE INCLUDE ADDITIONAL NOTES
 AS TO MINIMUM SILL HEIGHT, AND OPENING HEIGHT AND WIDTH
 OR SELECT THE PGT WINDOW TYPE IN THE CORRESPONDING
 PRODUCT APPROVAL TO ASSURE COMPLIANCE WITH FBCR-310.2.1
 -
 EMERGENCY AND ESCAPE RESCUE OPENINGS SHALL HAVE A NET
 CLEAR OPENING OF NOT LESS THAN 5.0 SQUARE FEET. THE NET
 CLEAR OPENING DIMENSIONS REQUIRED BY THIS SECTION SHALL
 BE OBTAINED BY THE NORMAL OPERATION OF THE EMERGENCY
 ESCAPE AND RESCUE OPENING FROM THE INSIDE. THE NET
 CLEAR HEIGHT OPENING SHALL BE NOT LESS THAN 24 INCHES
 (610 MM) AND THE NET CLEAR WIDTH SHALL BE NOT LESS THAN
 20 INCHES (508 MM). FBCR-310.2.2 ? THE MAXIMUM SILL
 HEIGHT IS 44?.
  
 10) SHEET A-1 THE DOOR SEPARATING THE GARAGE FROM THE
 UTILITY ROOM IS UNSPECIFIED IN TERMS OF FIRE
 RESISTANCE. PLEASE SPECIFY TO ASSURE COMPLIANCE WITH
 FBCR-302.5.1 OPEN PROTECTION. OPENINGS BETWEEN THE
 GARAGE AND RESIDENCE SHALL BE EQUIPPED WITH SOLID WOOD
 DOORS NOT LESS THAN 13/8 INCHES (35 MM) IN THICKNESS,
 SOLID OR HONEYCOMB-CORE STEEL DOORS NOT LESS THAN 13/8
 INCHES (35 MM) THICK, OR 20-MINUTE FIRE-RATED DOORS.
  
 11) SHEET A-2 THE WALL SECTION DOES NOT SPECIFY THE
 WALL INSULATION TYPE OR VALUE. PLEASE PROVIDE AN
 INDICATION CONSISTENT WITH THAT SPECIFIED IN THE ENERGY
 SUBMITTAL. ADDITIONALLY, THE NOTE RELATIVE TO CEILING
 INSULATION IS SLIGHTLY INCONSISTENT WITH BOTH THE
 ENERGY SUBMITTAL AND THE PRODUCT INFORMATION SUBMITTED.
 THE NOTE SPECIFIES AN R-19 VALUE WHERE THE ENERGY
 SUBMITTAL SPECIFIES R-20. PLEASE RECONCILE. PRESUMABLY
 R-20 IS TO BE USED IN A 5? THICKNESS PER TABLE 1 ON
 PAGE 6 OF 7 OF ESR-1826, PLEASE CONFIRM BY NOTATION OF
 THE USE OF CLASSIC PLUS. FBC-107; PLEASE PROVIDE THIS
 CONSISTENT MINIMUM PLAN REVIEW CRITERIA.
  
 12) SHEET A-2 CONTAINS A NOTE RELATIVE TO A WATER
 RESISTIVE BARRIER. ASSURE THE PROPOSED METHOD COMPLIES
 WITH FBCR-703.7.3 WATER-RESISTIVE BARRIERS SHALL BE
 INSTALLED AS REQUIRED IN SECTION R703.2 AND, WHERE
 APPLIED OVER WOOD-BASED SHEATHING, SHALL INCLUDE A
 WATER-RESISTIVE VAPOR-PERMEABLE BARRIER WITH A
 PERFORMANCE AT LEAST EQUIVALENT TO TWO LAYERS OF GRADE
 D PAPER. THE INDIVIDUAL LAYERS SHALL BE INSTALLED
 INDEPENDENTLY SUCH THAT EACH LAYER PROVIDES A SEPARATE
 CONTINUOUS PLANE AND ANY FLASHING (INSTALLED IN
 ACCORDANCE WITH SECTION R703.4) INTENDED TO DRAIN TO
 THE WATER-RESISTIVE BARRIER IS DIRECTED BETWEEN THE
 LAYERS.
  
 13) PLEASE NOTE THE TRUSS MANUFACTURER SUBMITTAL
 DOCUMENTS AS NOTED ON SHEET S-2 MAY BE A DEFERRED
 SUBMITTAL PRIOR TO TRUSS ERECTION PER FBCR802.10.1.
 TRUSS DESIGN DRAWINGS, PREPARED IN CONFORMANCE TO
 SECTION R802.10.1, SHALL BE PROVIDED TO THE BUILDING
 OFFICIAL AND APPROVED PRIOR TO INSTALLATION. TRUSS
 DESIGN DRAWINGS SHALL BE PROVIDED WITH THE SHIPMENT OF
 TRUSSES DELIVERED TO THE JOB SITE.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  
  