2018-04-30 13:32:59 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE COMPLETE ELECTRICAL PLAN FOR REVIEW, SIGNED |
| (AND SEALED, IF APPLICABLE) BY THE PERSON RESPONSIBLE |
| FOR THE DESIGN. INCLUDE ALL ELECTRICAL WORK. THE PLAN |
| PROVIDED DOES NOT SHOW ANY ELECTRICAL FOR THE KITCHEN |
| AREA THAT IS BEING RECONFIGURED. FS 471.003(2)(H); |
| 471.025, 481.229; WPB FBC 107.2.1, 107.3.5 |
| 2. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE |
| COMPLIANCE, A NOTE WILL SUFFICE. NEC 210.12; FBC RE |
| E3902.16 |
| 3. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1 |
| 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 6. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC |
| 107.3.5; FBC RE E3706.2, E3902 |
| 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| 8. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. |
| PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE |
| E3703.4, E3901.6 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |