2018-04-30 15:04:55 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. THE NAME OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR | | THE INFORMATION AND DESIGN IS ILLEGIBLE, PLEASE | | PROVIDE, FBC 107. | | | | 2. WINDOW DESIGN PRESSURES HAVE BEEN SPECIFIED AS PSI, | | REVISE TO PSF TO CORRELATE WITH BUILDING CODE | | REQUIREMENTS AND WITH PRODUCT APPROVALS, FBC R 301. | | | | 3. THE DETAIL FOR THE NEW WINDOW OPENING IS | | INSUFFICIENT; REVISE TO INCLUDE BAR SIZE, LENGTH, | | MINIMUM EMBEDMENT INTO EXISTING, FBC R 301. | | | | 4. AS THE BUILDING ENVELOPE IS AFFECTED, REVISE PLAN TO | | INCLUDE WIND DESIGN CRITERIA FBC R 301. | | | | | | |
|