Plan Review Notes
Plan Review Notes For Permit 18040448
Permit Number 18040448
Review Stop B
Sequence Number 1
Notes
Date Text
2018-04-30 15:04:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE NAME OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR
 THE INFORMATION AND DESIGN IS ILLEGIBLE, PLEASE
 PROVIDE, FBC 107.
  
 2. WINDOW DESIGN PRESSURES HAVE BEEN SPECIFIED AS PSI,
 REVISE TO PSF TO CORRELATE WITH BUILDING CODE
 REQUIREMENTS AND WITH PRODUCT APPROVALS, FBC R 301.
  
 3. THE DETAIL FOR THE NEW WINDOW OPENING IS
 INSUFFICIENT; REVISE TO INCLUDE BAR SIZE, LENGTH,
 MINIMUM EMBEDMENT INTO EXISTING, FBC R 301.
  
 4. AS THE BUILDING ENVELOPE IS AFFECTED, REVISE PLAN TO
 INCLUDE WIND DESIGN CRITERIA FBC R 301.
  
  
  