2018-06-25 07:18:066/25/2018 4TH PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT TWO LEGIBLE COPIES OF THE MANUFACTURER'S
 CERTIFIED PUMP CURVE IN ORDER TO VERIFY THE TDH
 CALCULATIONS AND MAXIMUM FLOW RATE BASED ON THOSE
 CALCULATIONS. APSP 7-13 SEC.4.4.9.1, INDICATE ON CURVE
 WHICH KEY CURVE APPLIES TO THIS SPECIFIC PUMP.
  