Plan Review Notes
Plan Review Notes For Permit 18040430
Permit Number 18040430
Review Stop P
Sequence Number 3
Notes
Date Text
2018-06-04 06:14:191) SHT. #7 - THE TDH CALCULATION WORKSHEET THAT HAS
 BEEN SUBMITTED IS BASED ON THE 2006 EDITION OF APSP 7.
 THE 2013 EDITION IS IN EFFECT AS OF DECEMBER 31, 2017.
 THE SIMPLIFIED TDH CALCULATION IS NO LONGER IN THE 2013
 APSP 7. REMOVE THIS SHEET FROM BOTH SETS OF PLANS.
 2) SHT. 5 - THIS SHEET NOTES THAT THE TDH CALCULATION
 IS BASED ON THE SIMPLIFIED TDH CALCULATION METHOD. THIS
 INFORMATION SHEET NEEDS TO BE DELETED FROM THE PLANS AS
 THE TDH SIMPLIFIED METHOD IS NO LONGER AN OPTION FOR
 DETERMINING MAXIMUM SYSTEM FLOW RATE.
 3) THE TDH CALCULATIONS SHALL BE THE TOTAL FROICTION
 LOSS OF THE PIPE, FITTINGS VALVES, FILTER,
 CHLORINATOR,ETC., ALL SYSTEM COMPONENTS EXCEPT THE
 PUMP.
 4) SUBMIT TWO LEGIBLE COPIES OF THE MANUFACTURER'S
 CERTIFIED PUMP CURVE IN ORDER TO VERIFY THE TDH
 CALCULATIONS AND MAXIMUM FLOW RATE BASED ON THOSE
 CALCULATIONS. APSP 7-13 SEC.4.4.9.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  