Plan Review Notes For Permit 18040430 |
Permit Number |
18040430 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-06-04 06:14:19 | 1) SHT. #7 - THE TDH CALCULATION WORKSHEET THAT HAS | | BEEN SUBMITTED IS BASED ON THE 2006 EDITION OF APSP 7. | | THE 2013 EDITION IS IN EFFECT AS OF DECEMBER 31, 2017. | | THE SIMPLIFIED TDH CALCULATION IS NO LONGER IN THE 2013 | | APSP 7. REMOVE THIS SHEET FROM BOTH SETS OF PLANS. | | 2) SHT. 5 - THIS SHEET NOTES THAT THE TDH CALCULATION | | IS BASED ON THE SIMPLIFIED TDH CALCULATION METHOD. THIS | | INFORMATION SHEET NEEDS TO BE DELETED FROM THE PLANS AS | | THE TDH SIMPLIFIED METHOD IS NO LONGER AN OPTION FOR | | DETERMINING MAXIMUM SYSTEM FLOW RATE. | | 3) THE TDH CALCULATIONS SHALL BE THE TOTAL FROICTION | | LOSS OF THE PIPE, FITTINGS VALVES, FILTER, | | CHLORINATOR,ETC., ALL SYSTEM COMPONENTS EXCEPT THE | | PUMP. | | 4) SUBMIT TWO LEGIBLE COPIES OF THE MANUFACTURER'S | | CERTIFIED PUMP CURVE IN ORDER TO VERIFY THE TDH | | CALCULATIONS AND MAXIMUM FLOW RATE BASED ON THOSE | | CALCULATIONS. APSP 7-13 SEC.4.4.9.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | | | |
|