Plan Review Notes
Plan Review Notes For Permit 18040410
Permit Number 18040410
Review Stop B
Sequence Number 5
Notes
Date Text
2019-08-07 17:55:57***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 5TH BUILDING REVIEW DENIED:
  
 1. PROVIDE PRODUCT APPROVALS REVIEWED AND APPROVED BY
 DESIGNER OF RECORD.
  
 2. PROVIDE UPDATED ENERGY CALCULATIONS THAT CORRELATE
 WITH PLANS.
 (THE DOORS AND WINDOWS FROM THE PLANS NEED TO BE
 INCLUDED IN THE ENERGY CALCULATIONS).
  
 3. THE ELEVATION CERTIFICATE NEEDS TO BE CORRECTED,
 (SEE SUBMITTAL # 19080006).
  
 PROVISO: THE INSULATION AT BLOCK WALLS NEEDS TO
 CORRELATE WITH INSULATION ON ENERGY CALCULATIONS AS
 FOLLOWS (R=4.2).
  
  