Plan Review Notes
Plan Review Notes For Permit 18040410
Permit Number 18040410
Review Stop B
Sequence Number 4
Notes
Date Text
2019-03-25 15:01:0703/25/19 RESPONSE TO SHUBHAM GOWDA E-MAIL
 GOOD AFTERNOON SHUBHAM,
 THAT ELEVATION CERTIFICATE IS TOO OLD. IT LOOKS TO BE
 DONE BEFORE THE ADDITION. IT?S DATED 2010/01/05 BY
 CLYDE MCNEAL.
 THE ELEVATION CERTIFICATES WE NEED ARE THE ONES THAT
 ARE DONE DURING CONSTRUCTION. IMPORTANT: THIS PERMIT
 WAS ISSUED PRIOR TO THE FEMA REVISED FLOOD MAPS. THE
 FINISH FLOOR ELEVATIONS WERE DONE BASED ON NGVD29
 VERTICAL DATUM. KEEP THIS IN MIND WHEN SUBMITTING THE
 ELEVATION CERTIFICATES.
 IF SURVEYOR USES NAVD 1988, THEN CONVERSION TO NGVD 29
 WILL NEED TO BE PROVIDED.
 THANK YOU
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  
  
  
 RESIDENTIAL (R3) REVISION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- A) OK. SAME ARCH.
  
 B) OK.
  
 C) OK.
  
 D) OK.
  
  
 ORIGINAL COMMENT:
 2- SIZE OF ENTRY DOOR DOESN'T COMPLY WITH SEC. R311.2
 FBC-RESIDENTIAL. NEED 32" MIN. CLEAR OPENING. REVISE AS
 REQUIRED. TYPICALLY 36" DOORS ARE THE ONES THAT COMPLY.
  
 RESPONSE:
 RESPONSE LETTER STATES "STRUCTURAL ENGINEER HAS REVISED
 S-1 SHEET TO SHOW CORRECT DOOR OPENING SIZE". SHEET S-1
 SHOWS 5'-4" OPENING SIZE. DOUBLE 3'X8' DOORS DON'T FIT
 IN THIS OPENING. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 ORIGINAL COMMENT:
 3- SPECIFY ON PLANS THE EXISTING HOUSE AND EQUIPMENT
 FINISH FLOOR ELEVATION AND THE PROPOSED ADDITION AND
 EQUIPMENT FINISH FLOOR ELEVATION. SEC. 94-546 CITY
 ORDINANCE. NOTE: APPROVED PLANS SPECIFIED THE EXISTING
 AND PROPOSED FINISH FLOOR ELEVATION TO BE 8.05'. BEFORE
 10/05/17 CITY ORDINANCE REQUIRED 1 FOOT FREE BOARD
 ABOVE THE BASE FLOOD ELEVATION. THEREFORE, THIS
 ELEVATION WAS IN COMPLIANCE. ELEVATION CERTIFICATES
 WILL BE REQUIRED DURING CONSTRUCTION.
  
 RESPONSE:
 REPEAT COMMENT. ELEVATION CERTIFICATES HAVE NOT BEEN
 SUBMITTED FOR REVIEW.
  
 ORIGINAL COMMENT:
 4- SHEET S-6: DOORS AND WINDOWS DESIGN PRESSURES SHOWN
 ON 1ST AND 2ND FLOOR PLAN DON'T MATCH DESIGN PRESSURES
 SHOWN ON THE TABLE ON SAME SHEET. REVISE AS REQUIRED TO
 MATCH. ALSO, DESIGN PRESSURES CAN NOT BE LOWER ON THE
 SECOND FLOOR THAN THE FIRST FLOOR. DESIGN PRESSURES CAN
 NOT BE LOWER FOR OPENINGS THAT ARE SMALLER. REVISE AS
 REQUIRED. NOTE: THE EDGE DISTANCE IS 4'-0" MIN AS
 REQUIRED BY NOTE AT THE BOTTOM OF FIGURE R301.2(7)
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
 RESPONSE LETTER STATES "STRUCTURAL ENGINEER HAS REVISED
 S-6 TO SHOW WIND PRESSURES". DRAWING WAS NOT REVISED.
  
 5- OK.
  
 4- OK.
  
 ORIGINAL COMMENT:
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR SECOND FLOOR BALCONY DECK COVERING.
 AND, CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING
 TO BE USED. NOTE: COORDINATE WITH ITEM #5 ABOVE.
  
 RESPONSE:
 REPEAT COMMENT. PRODUCT APPROVAL NOT SUBMITTED.
  
 6- OK.
  
 IMPORTANT NOTES:
 (1) ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION. (********ELEVATION CERTIFICATES NO
 PROVIDED YET AS OF 03/19/19).
 (2)GARAGE FLOOD VENTS NEED TO BE INSTALLED BELOW THE
 BASE FLOOD ELEVATION (********ELEVATION CERTIFICATES NO
 PROVIDED YET AS OF 03/19/19).
 (3) ORIGINAL PERMIT WAS APPROVED WITH PROVISO. PROVIDE
 REQUIRED INFORMATION . SEE COPY OF PROVISO BELOW.
 (*****NOT ADDRESSED YET AS OF 03/19/19).
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  
  
 BUILDING REVIEW APPROVED WITH PROVISO: ******(DATED
 02/01/17)
 1- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE
 INSTALLATION OF BRICK VENEER, INCLUDING VENEER SUPPORTS
 AT OPENINGS. ALSO, SPECIFY WEEP-HOLES, ETC.
 NOTE: PROVIDE COMPLETE DETAILS/ SPECIFICATIONS. DON'T
 CITE CODE SECTIONS.
  
 2- ENERGY CALCULATIONS WERE REVISED FOR FULL HOUSE
 COMPLIANCE INSTEAD OF ADDITION ALONE:
 A) REVISE CEILING INSULATION ITEM #10 TO MATCH PLANS.
 VENTED AND UNVENTED ROOFS.
 B) REVISE ROOF MATERIAL SHOWN ON PAGE 2 OF 5 TO MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED.
 C) REVISE CONCRETE BLOCK INSULATION ITEM #9 DOESN'T
 MATCH PLANS. SEE DETAIL #2 ON SHEET A-10.
 D) REVISE R-VALUE SHOWN ON THE CEILING INSULATION ON
 PAGE 3 OF 5 TO MATCH PLANS AND INFORMATION SHOWN ON
 ITEM #10.
 E) REVISE DOOR TYPE SPECIFIED ON PAGE 3 OF 5 TO MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. THERE ARE NO
 INSULATED DOORS. DOORS WITH GLASS NEED TO BE INCLUDED
 IN THE WINDOWS AREA.
 F) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS.
 G) REVISE NUMBER OF OCCUPANTS ON PAGE 2 OF 5. WHY 20
 PEOPLE IN A SINGLE FAMILY RESIDENCE.
 H) REVISE FLOOR TYPES ON PAGE 2 OF 5. 2ND FLOOR IS NOT
 ON SLAB ON GRADE.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE DOORS THAT MEETS ALL THE DESIGN LOADS SHOWN
 ON SHEET S-6 (POSITIVE AND NEGATIVE).
 B) DOUBLE EXTERIOR DOORS THAT MEET THE DESIGN PRESSURES
 SPECIFIED ON PLANS.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS.