Plan Review Notes For Permit 18040406 |
Permit Number |
18040406 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-04-10 18:22:56 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017). | | | | 1- ROOF TILE UNDERLAYMENT PROPOSED APPLICATION IS NOT | | CLEAR. ACCORDING TO POLYGLASS FLORIDA PRODUCT APPROVAL | | FL5259-R27 SUBMITTED THE CONCRETE TILE IS GOING TO BE | | FASTENED USING AH-160 ADHESIVE. UNDERLAYMENT SYSTEM #10 | | FROM SEC. 5.6.4 WAS HIGHLIGHTED. THE MAXIMUM DESIGN | | PRESSURE FOR #10 ASSEMBLY IS -45PSF. THIS ASSEMBLY | | DOESN'T MEET THE DESIGN PRESSURES FOR THE PERIMETER AND | | CORNER AREAS OF THIS HOUSE LOCATED IN EXPOSURE "C". IF | | USING THIS ASSEMBLY, THEN NEED TO PROVIDE SIGNED AND | | SEALED RAS 117 CALCULATIONS FOR PERIMETER AND CORNER | | AREAS AS REQUIRED BY HIGHLIGHTED SEC. 5.6.4.2 ON SAME | | FLORIDA PRODUCT APPROVAL. | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY | | REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|