2018-04-10 18:22:56RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- ROOF TILE UNDERLAYMENT PROPOSED APPLICATION IS NOT
 CLEAR. ACCORDING TO POLYGLASS FLORIDA PRODUCT APPROVAL
 FL5259-R27 SUBMITTED THE CONCRETE TILE IS GOING TO BE
 FASTENED USING AH-160 ADHESIVE. UNDERLAYMENT SYSTEM #10
 FROM SEC. 5.6.4 WAS HIGHLIGHTED. THE MAXIMUM DESIGN
 PRESSURE FOR #10 ASSEMBLY IS -45PSF. THIS ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR THE PERIMETER AND
 CORNER AREAS OF THIS HOUSE LOCATED IN EXPOSURE "C". IF
 USING THIS ASSEMBLY, THEN NEED TO PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS FOR PERIMETER AND CORNER
 AREAS AS REQUIRED BY HIGHLIGHTED SEC. 5.6.4.2 ON SAME
 FLORIDA PRODUCT APPROVAL.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS.
  
  