2018-04-16 11:23:361ST REVIEW FBC-2017 MECHANICAL , EXISTING BUILDING CODE
 PERMIT #18040368
 4/16/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 809.2: REFER TO SECTION 809.2 FBC-17 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3.1
 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) SHEET M-2: PLEASE ADD THE TEXT FOR KEYED NOTE #5
  
  