Plan Review Notes
Plan Review Notes For Permit 18040368
Permit Number 18040368
Review Stop B
Sequence Number 1
Notes
Date Text
2018-04-16 18:14:30COMMERCIAL INTERIOR TENANT BUILDOUT, BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- ADDRESS OF PROPOSED WORK IS NOT CLEAR. PERMIT
 APPLICATION STATES 831 VILLAGE BLVD #109. ARCHITECTURAL
 PLANS STATES 931 VILLAGE BLVD #109 AND CITY RECORDS
 (BASED ON THE PARCEL ID #) IDENTIFIES THIS BUILDING AS
 731 VILLAGE BLVD #109. PLEASE COORDINATE CORRECT
 ADDRESS TO AVOID CONFLICT/DELAYS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 NOTE: COORDINATE CORRECT ADDRESS WITH MICHAEL P ORIO
 GIS SUPPORT SPECIALIST
 INFORMATION TECHNOLOGY
 GIS
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1080
 FAX: 494-1117
 E-MAIL: [email protected]
  
 2- BUILDING CODE INFORMATION ON SHEET A-0.10:
 A) ACCORDING TO PLANS SUBMITTED THE TENANT BUILDOUT IS
 NOT MERCANTILE. IT LOOKS MORE LIKE BUSINESS GROUP
 CLASSIFICATION. SEE SEC. 304.1 FBC. IT LOOKS LIKE ALL
 THE INFORMATION PROVIDED IN THIS TABLE IS BASED ON
 MERCANTILE OCCUPANCY (ALLOWABLE AREA, BUILDING HEIGHT,
 OCCUPANT LOAD, ETC). REVISE ALL THE INFORMATION TO
 REFLECT THE CORRECT USE AND OCCUPANCY. SEC. 301.1 FBC.
 NOTE: THIS IS A BUILDING WITH MULTIPLE TENANTS. SEE
 SEC. 508.1 FBC. CLARIFY WHY THE THE OCCUPANCY
 SEPARATION AND TENANT SEPARATION IS N/A?
  
 B) CLARIFY/REVISE THE REQUIRED AND PROVIDED DIMENSIONS
 SHOWN UNDER "OTHER EGRESS COMPONENTS (0.2" PER
 OCCUPANT)". IT LOOKS LIKE THE REQUIREMENTS FOR
 STAIRWAYS SEC. 1005.3.1 FBC AND THE REQUIREMENTS FOR
 OTHER EGRESS COMPONENTS SEC. 1005.3.2 ARE MISMATCHED.
 REVISE AS REQUIRED AND PROVIDE CORRECT INFORMATION.
  
 C) CLARIFY WHERE IN THE FLOOR PLAN IS THE 36" MINIMUM
 CLEAR OPENING SPECIFIED UNDER THE PROVIDED COLUMN. SEC.
 107.2.1 CITY AMENDMENTS.
  
 D) CLARIFY WHY THE MIN. CORRIDOR WIDTH IS N/A UNDER THE
 PROVIDED COLUMN?. TABLE 1020.2 FBC.
  
 3- LIFE SAFETY PLAN ON SHEET A-0.10 IS MISSING THE
 EMERGENCY EXIT SIGN ABOVE THE DOOR BY THE DEMONSTRATION
 AREA AS REQUIRED BY SEC. 1025.2.6.1 FBC
  
 4- EGRESS IS NOT ALLOWED THROUGH STORAGE ROOMS. REVISE
 PROPOSED FLOOR PLAN AND LIFE SAFETY PLAN AS REQUIRED.
 SEE SEC. 1016.2 FBC.
  
 5- WINDOWS AND DOORS DESIGN PRESSURES SPECIFIED ON
 SHEET A-4.00. SPECIFY THE BUILDING MEAN ROOF HEIGHT,
 BUILDING EXPOSURE, OPENING LOCATION (INTERIOR OR END).
 NOTE: THE DESIGN PRESSURES NEED TO BE BASED ON THE
 TRIBUTARY AREA OF THE WINDOW/DOORS. REVISE DESIGN
 PRESSURES ACCORDINGLY. SEC. 1609.6.4.4.1 FBC
  
 6- SHEET A-4.00:
 A) IT LOOKS LIKE THE DOOR ON THE RESTROOM DOESN'T
 COMPLY WITH THE 18" MINIMUM MANEUVERING CLEARANCE
 REQUIRED FOR A FRONT APPROACH. REVISE FLOOR PLANS AND
 DETAILS AS REQUIRED. SEE SEC. 404.2.4 FBC-ACCESSIBILITY
  
 B) REVISE THE CLEAR FLOOR SPACE DIMENSIONS SHOWN ON THE
 ENLARGED R.R PLAN. PLANS AND ELEVATIONS SHOW A FLOOR
 MOUNTED WATER CLOSET. ACCORDING TO SEC. 604.8.1.1
 FBC-ACCESSIBILITY FLOOR MOUNTED WATER CLOSETS REQUIRE
 60 INCHES WIDE MINIMUM AND 59 INCHES DEEP MINIMUM (NOT
 56") CLEAR FLOOR SPACE.
  
 C) REVISE THE DIMENSION SHOWN FOR THE MIRROR ON DETAIL
 "A". THE DIMENSION IS TO THE BOTTOM EDGE OF THE
 REFLECTING SURFACE NOT TO THE BOTTOM EDGE OF THE MIRROR
 FRAME. SEE SEC. 603.3 FBC ACCESSIBILITY AND REVISE AS
 REQUIRED.
  
 D) REVISE THE DIMENSION SHOWN FOR THE HEIGHT OF THE
 GRAB BARS. ACCORDING TO SEC. 609.4 ACCESSIBILITY THE
 DIMENSION IS MEASURED TO THE TOP OF THE GRIPPING
 SURFACE NOT TO THE CENTER LINE OF THE GRAB BAR. REVISE
 AS REQUIRED.
  
 E) REVISE DIMENSION SHOWN FOR THE TOILET PAPER
 DISPENSER. ACCORDING TO SEC. 604.7 FBC-ACCESSIBILITY
 THE DIMENSION IS MEASURED TO THE CENTERLINE OF THE
 DISPENSER NOT TO THE EDGES. REVISE AS REQUIRED,
 INCLUDING THE DIMENSIONS FROM THE EDGE OF THE WATER
 CLOSET AND FROM THE FINISH FLOOR.
  
 F) DETAIL "C" IS NOT DRAWN TO SCALE. THE ROOM DOESN'T
 MEASURE 6'-0". REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOORS WITH TRANSOM ABOVE AS SHOWN ON PLANS.
  
 B) STOREFRONT WINDOWS AS SHOWN PLANS. NOTE: IDENTIFY
 GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS
 AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017
 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL
 BE INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]