2018-04-27 15:49:32 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| LOADS. THE CURRENT CALCULATION PROVIDED DID NOT INCLUDE |
| THE 3 VA PER SQUARE FOOT. NEC 220; FBC RE E3602.2 |
| 2. RISER DIAGRAM SHOWS #1 WIRE TO INTERIOR PANEL. THIS |
| WIRE IS NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC |
| 310.15(B)(16); FBC RE E3603.1, E3705.1 |
| 3. CURRENT NOTE FOR AFCI PROTECTION IS NOT CODE |
| COMPLIANT. PER CODE: ?ALL BRANCH CIRCUITS THAT SUPPLY |
| 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS |
| INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS, |
| LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, |
| SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS, |
| LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI |
| PROTECTED.? PROVIDE CORRECTION. NEC 210.12; FBC RE |
| E3902.16 |
| 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 5. PLAN DOES NOT CLARIFY WHAT TYPE OF LIGHT FIXTURES |
| ARE USED ABOVE BATH SHOWER AS THE SYMBOL USED IS NOT IN |
| LEGEND. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE |
| SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC |
| 410.10(D); FBC RE E4003.11 |
| 6. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7 |
| 7. CONTRACT PROVIDED DOES NOT LIST ELECTRICAL IN TOTAL. |
| PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF |
| WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |