2018-04-27 15:49:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE CURRENT CALCULATION PROVIDED DID NOT INCLUDE
 THE 3 VA PER SQUARE FOOT. NEC 220; FBC RE E3602.2
 2. RISER DIAGRAM SHOWS #1 WIRE TO INTERIOR PANEL. THIS
 WIRE IS NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC
 310.15(B)(16); FBC RE E3603.1, E3705.1
 3. CURRENT NOTE FOR AFCI PROTECTION IS NOT CODE
 COMPLIANT. PER CODE: ?ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED.? PROVIDE CORRECTION. NEC 210.12; FBC RE
 E3902.16
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 5. PLAN DOES NOT CLARIFY WHAT TYPE OF LIGHT FIXTURES
 ARE USED ABOVE BATH SHOWER AS THE SYMBOL USED IS NOT IN
 LEGEND. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE E4003.11
 6. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 7. CONTRACT PROVIDED DOES NOT LIST ELECTRICAL IN TOTAL.
 PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF
 WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  