2018-04-30 10:01:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PROVIDE A DETAIL FOR THE AWNINGS, FBC R 301. PLAN
 STATES THAT THEY WILL BE REPLACED. IT APPEARS THAT THEY
 ARE STRUCTURAL AWNINGS INCLUDING FRAMING AND ROOFING.
  
 2. VALUE APPEARS LOW; PROVIDE A COST BREAKDOWN FBC 109.
  
 3. AS WINDOW INSTALLATION IS A SIGNIFICANT PORTION OF
 PROPOSED WORK, PROVIDE PRODUCT APPROVALS. PRODUCT
 APPROVALS TO BE REVIEWED BY DESIGNER OF RECORD PRIOR TO
 INSTALLATION. (SINGLE HUNG, MULLION) FBC R 301.
  
 4. S1 WINDOW SCHEDULE IS INCOMPLETE; REVISE TO INCLUDE
 PROPOSED WINDOWS FOR OPENINGS L, M, N.
  
  
  