2018-04-10 09:14:1904/10/18 DENIED BY PLUMBING
  
 1. FIRE BACKLOW INSTALLATION SHALL BE DONE BY QUALIFIED
 CONTRACTOR, THE 2017 FLORIDA STATUTES 633.102,
 INSURANCE, CHAPTER 633, FIRE PREVENTION AND CONTROL, 3
 (A) CONTRACTOR I, II AND V ARE THE ONLY ONES LICENSED
 CONTRACTOR WHOSE BUSINESS INCLUDES THE EXECUTION OF
 CONTRACTS REQUIRING THE ABILITY TO LAY OUT, FABRICATE,
 INSTALL, INSPECT, ALTER, REPAIR, AND SERVICE ALL TYPES
 OF FIRE PROTECTION SYSTEMS, EXCLUDING PRE-ENGINEERED
 SYSTEMS. PLEASE PROVIDE PROPER PAPERWORK SUPPORTING THE
 LICENSE FOR THIS TYPE OF WORK, A LICENSE CONTRACTOR THE
 FOR THE SCOPE OF WORK, ONE IN REFERENCE TO THIS
 APPLICATION IS A UTILITY CONTRACTOR AND THEY ARE NOT
 ALLOWED TO THE WORK ACCORDING TO THE SCOPE OF WORK
 UNDER THEIR LICENSE. THEY ARE NOT ALLOWED TO WORK
 ANYTHING THAT GOES BEYOND THE METER. "AN UNDERGROUND
 UTILITY CONTRACTOR SHALL NOT INSTALL ANY PIPING THAT IS
 AN INTEGRAL PART OF A FIRE
 PROTECTION SYSTEM, BEGINNING AT THE POINT WHERE THE
 PIPING IS USED EXCLUSIVELY FOR SUCH SYSTEM." HTTP://DIS
 COVER.PBCGOV.ORG/PZB/CONTRACTORS/FORMS/STANDARDS.PDF
 (ITEM 39)
  
 2. ALL DOMESTIC BACKFLOW MUST BE CERTIFIED BY UTILITIES
 PRIOR TO FINAL INSPECTION. PLEASE CONTACT CITY OF WPB
 UTILITIES AT 561-822-2240 FOR FURTHER DIRECTIONS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  
  