Date |
Text |
2018-04-30 12:53:43 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. IT APPEARS THAT THE WRONG CODE WAS USED FOR DESIGN |
| AS THERE ARE SEVERAL CODE SECTIONS QUOTED FROM THE FBC, |
| RESIDENTIAL. THE PROVISIONS OF THE FLORIDA BUILDING |
| CODE, RESIDENTIAL SHALL APPLY TO THE CONSTRUCTION, |
| ALTERATION, MOVEMENT, ENLARGEMENT, REPLACEMENT, REPAIR, |
| EQUIPMENT, USE AND OCCUPANCY, LOCATION, REMOVAL AND |
| DEMOLITION OF DETACHED ONE- AND TWO-FAMILY DWELLINGS |
| AND TOWNHOUSES NOT MORE THAN THREE STORIES ABOVE GRADE |
| PLANE IN HEIGHT WITH A SEPARATE MEANS OF EGRESS AND |
| THEIR ACCESSORY STRUCTURES NOT MORE THAN THREE STORIES |
| ABOVE GRADE PLANE IN HEIGHT. REMOVE ANY NOTES THAT |
| QUOTE THE FBC RESIDENTIAL CODE.PROVIDE CORRECTION. FBC |
| RE R101.2; FBC 107.2.1 |
| 2. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D) |
| 3. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| NOTE WILL SUFFICE. NEC 406.12 |
| 4. SHOW LOCATION OF PANEL TO BE RELOCATED TO CONFIRM |
| CODE COMPLIANCE. FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |