2018-04-20 18:51:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE FLAME SPREAD TEST (ASTME-84), SENT VIA EMAIL,
 WAS PERFORMED WITH A FIBER CEMENT BOARD TOWARDS THE
 FLAME IN THE STEINER TUNNEL. THIS IS NOT THE FLOORING
 MATERIAL PROPOSED (FIBER CEMENT BOARD). IT IS NOT CLEAR
 WHY THEY DID NOT HAVE THE TEST DONE WITH THE
 UNDERLAYMENT SIDE TO FLAME, OR HAVE A SAMPLE TESTED
 WHICH WAS THE FLOORING ASSEMBLY PROPOSED - LVT AND
 UNDERLAYMENT ON A SUPPORTING NON COMBUSTIBLE BOARD OR
 SLAB, FBC B 603.1.
  