Plan Review Notes For Permit 18040341 |
Permit Number |
18040341 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-04-20 18:49:35 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. THE FLAME SPREAD TEST (ASTME-84), SENT VIA EMAIL, | | WAS PERFORMED WITH A FIBER CEMENT BOARD TOWARDS THE | | FLAME IN THE STEINER TUNNEL. THIS IS NOT THE FLOORING | | MATERIAL PROPOSED (FIBER CEMENT BOARD). IT IS NOT CLEAR | | WHY THEY DID NOT HAVE THE TEST DONE WITH THE | | UNDERLAYMENT SIDE TO FLAME, OR HAVE A SAMPLE TESTED | | WHICH WAS THE FLOORING ASSEMBLY PROPOSED - LVT AND | | UNDERLAYMENT ON A SUPPORTING NON COMBUSTIBLE BOARD OR | | SLAB, FBC B 603.1. | | |
|