Plan Review Notes
Plan Review Notes For Permit 18040160
Permit Number 18040160
Review Stop P
Sequence Number 2
Notes
Date Text
2018-05-17 09:51:421) THE PUMP CURVE ON SHT.3 OF 4 IS TOO SMALL TO READ
 THE MAX. SYSTEM FLOW RATE BASED ON THE TOTAL DYNAMIC
 HEAD. SUBMIT AN EXPANDED AND LEGIBLE PUMP CURVE FOR
 REVIEW.WPB AMEND. TO FBC SEC. 107.2.1.
 2) IDENTIFY ON THE PUMP CURVE WHICH PUMP CURVE KEY IS
 APPLICABLE FOR THE SPECIFIC PUMP BEING INTALLED ON THIS
 POOL. SUBMIT THE PART NUMBER OF THE PUMP FOR
 IDENTIFICATION ON THE PUMP CURVE.WPB AMEND. TO FBC SEC.
 107.2.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW