2018-05-17 09:51:42 | 1) THE PUMP CURVE ON SHT.3 OF 4 IS TOO SMALL TO READ | | THE MAX. SYSTEM FLOW RATE BASED ON THE TOTAL DYNAMIC | | HEAD. SUBMIT AN EXPANDED AND LEGIBLE PUMP CURVE FOR | | REVIEW.WPB AMEND. TO FBC SEC. 107.2.1. | | 2) IDENTIFY ON THE PUMP CURVE WHICH PUMP CURVE KEY IS | | APPLICABLE FOR THE SPECIFIC PUMP BEING INTALLED ON THIS | | POOL. SUBMIT THE PART NUMBER OF THE PUMP FOR | | IDENTIFICATION ON THE PUMP CURVE.WPB AMEND. TO FBC SEC. | | 107.2.1. | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | | | | | | | |
|