Plan Review Notes
Plan Review Notes For Permit 18040160
Permit Number 18040160
Review Stop P
Sequence Number 1
Notes
Date Text
2018-04-12 17:14:3604/12/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) SHOW HOW SYSTEM IS SIZED BASED ON TDH AND NOT THE
 PUMP CURVE TO COMPLY WITH ANSI/ APSP/ ICC-7 2013
  
 2) PAGE 2 NOTE #7 OF GENERAL NOTES. PLEASE REMOVE AIR
 TEST. AIR TEST IS NOT PERMITTED PER FBC-R P2503.7 AND
 MANUFACTURES INSTALLATION GUIDELINES FBC-R P2609.2.
 THIS IS ALSO A SAFTEY ISSUE TO THE INSTALLERS AND
 INSPECTORS ON-SITE.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT