Plan Review Notes For Permit 18040160 |
Permit Number |
18040160 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-04-12 17:14:36 | 04/12/2018 1ST PLUMBING REVIEW**DENIED** | | | | 1) SHOW HOW SYSTEM IS SIZED BASED ON TDH AND NOT THE | | PUMP CURVE TO COMPLY WITH ANSI/ APSP/ ICC-7 2013 | | | | 2) PAGE 2 NOTE #7 OF GENERAL NOTES. PLEASE REMOVE AIR | | TEST. AIR TEST IS NOT PERMITTED PER FBC-R P2503.7 AND | | MANUFACTURES INSTALLATION GUIDELINES FBC-R P2609.2. | | THIS IS ALSO A SAFTEY ISSUE TO THE INSTALLERS AND | | INSPECTORS ON-SITE. | | | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] | | |
|