2018-05-03 13:30:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 3. METAL ROOF - THE AREA ATTRIBUTED TO A FASTENER IS TO
 BE USED TO DETERMINE DESIGN PRESSURES. SEE SHEET S004,
 DESIGN PRESSURES, ZONE 5 (PITCHED ROOF) DP REQUIREMENT
 IS -72.10 FOR ZONE 2H, 20SF. THE FASTENING PROPOSED HAS
 A LIMITATION OF -60PSF; PLEASE ADDRESS.
  
 IN THE FUTURE, PLEASE CONSIDER SUBMITTING DIGITALLY AS
 YOUR ENGINEER (WARTER, PE) HAS A DIGITAL SIGNATURE.
  
  
  
  