2018-10-23 09:56:20 | 3RD REVIEW- FBC-2017 MECHANICAL |
| PERMIT #18040104 |
| 10/23/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M2.1: AS PREVIOUSLY NOTED THERE APPEARS TO BE |
| AN INADEQUATE AMOUNT OF O/A PROVIDED TO THE BASEMENT |
| ROOMS AND SPACES FOR OCCUPANTS, AND FOR MAKEUP AIR FOR |
| THE BATHROOM EXHAUST. THE CURRENT PLAN SHOWS ONLY 135 |
| CFMS PROVIDED TO LOUNGE 003 FROM THE OARTU WHICH IS NOT |
| IN COMPLIANCE WITH TABLE 403.3.1.1 AND SECTION 501.4. |
| IN ADDITION PLEASE NOTE THE |
| |
| FOLLOWING: A) THE OARTU SCHEDULE ON SHEET M7.1 HAS A |
| CAPACITY OF 2730 CFMS, AND THE AIR BALANCE SCHEDULE ON |
| M7.2 INDICATES 400 CFMS TO BE PROVIDED TO THE BASEMENT |
| AND 855 CFMS TO THE FIRST FLOOR. THIS DATA APPEARS TO |
| INDICATE A MISTAKE IN SYSTEM SELECTION. B) THE RTU #2 |
| SCHEDULE ON M7.1 INDICATES THE UNIT HAS AN O/A CAPACITY |
| OF 1387 CFMS, HOWEVER THE AIR BALANCE |
| |
| SCHEDULE INDICATES A REQUIREMENT OF 2705 CFMS. AGAIN AN |
| APPARENT MISTAKE IN SYSTEM SELECTION. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |