2018-08-15 07:50:592ND REVIEW- PART 2, FBC-2017 MECHANICAL
 PERMIT #18040104
 8/21/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE FOLLOWING COMMENTS ARE BASED ON THE 1ST REVIEW
 COMMENTS WHICH STILL EXIST EITHER PARTIALLY OR
 COMPLETELY .
  
 1) THE REQUESTED ELECTRONICALLY SIGNED AND SEALED
 ENERGY AND AC CALCULATIONS WERE NOT PROVIDED.
  
 2) THE ENERGY COMPLIANCE FORM IS INDICATING THE VRF
 UNITS ARE "WATER SOURCE" BUT THAT DOES NOT MATCH WITH
 THE EQUIPMENT SCHEDULES PROVIDED ON THE PLANS WHICH
 INDICATE AIR SOURCE UNITS- SEE TABLE C403.2.3(11) FBC
 EC.
  
 3) THE ENERGY COMPLIANCE FORM DOES NOT LIST ANY DATA
 FOR RTU-2 (528.2 MBH) AND THE OARTU (107.1 MBH) -
 PLEASE PROVIDE THE DATA.
  
 4) M7.1 & M7.2: THE ENERGY COMPLIANCE FORM LISTS RTU-1
 AS A 93.3 MBH UNIT, HOWEVER THERE IS NO RTU-1 IN THE
 SCHEDULES OR WITH THAT COOLING CAPACITY.
  
 5) AS PREVIOUSLY NOTED IN THE FIRST REVIEW, THERE IS NO
 COMPLIANCE DATA LISTED IN THE ENERGY COMPLIANCE FORM
 FOR AHU'S 5, 6, 7, & 8.
  
 6) REFER TO SHEETS M2.5, M6.1 AND M7.1: PLEASE CORRECT
 THE LABELING OF THE LARGE 528.2 MBH RTU WHICH IS
 INDICATED AS RTU-2 ON THE PLANS, AND RTU-1 IN THE
 SCHEDULE.
  
 7) SHEETS ALS.01 AND M0.1 HAVE NOT BEEN UPDATED TO LIST
 THE CORRECT CODE EDITIONS AND THE CORRECT NOA # FOR THE
 ROOF STAND.
  
 8) SHEET M6.1: PLEASE PROVIDE EXHAUST VENTILATION
 CALCULATIONS AND AIR BALANCE CALCULATIONS ON THE PLAN.
  
 9) SHEET M2.1: PLEASE CLARIFY HOW O/A IS BEING PROVIDED
 TO THE LOUNGE ROOM THAT IS CLOSE TO THE STAIRCASE, AND
 HOW MAKEUP AIR IS BEING PROVIDED FOR THE TOILET ROOM
 EXHAUST SYSTEM.
  
 10) SHEET M2.2: REFER TO SECTION 502.13 FBC M AND
 CLARIFY HOW THE EXHAUST VENTILATION SYSTEM IN THE
 GARAGE WILL OPERATE- CONTINOUSLY OR IN ACCORDANCE WITH
 SECTION 404. PLEASE PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE GARAGE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
 2ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18040104
 8/15/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 2ND REQUEST FOR ELECTRONICALLY SIGNED AND SEALED
 ENERGY AND AC CALCULATIONS- SEE COMMENT #1 FROM THE 1ST
 REVIEW.
  
 2) ACCORDING TO THE RESPONSE NARRATIVE TO THE 1ST
 REVIEW COMMENTS, SHEETS M0.1, M2.1, M2.5, M6.1, AND
 M7.1 HAVE BEEN REVISED, HOWEVER THOSE SHEETS HAVE NOT
 BEEN UPDATED, AND M6.1 HAS BEEN REPLACED WITH E.01. THE
 REVIEW IS STOPPED AT THIS POINT UNITL REVISED SHEETS
 ARE UPLOADED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  