2018-07-24 14:01:30PERMIT # 18040104
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW COMMENTS:
  
 1) BECAUSE THIS BUILDING DOES NOT HAVE AN EXISTING FIRE
 SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM: ENGINEERED
 FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION DOCUMENTS
 ARE REQUIRED FOR A GENERAL/MASTERL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 2) PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR