Plan Review Notes
Plan Review Notes For Permit 18040104
Permit Number 18040104
Review Stop B
Sequence Number 2
Notes
Date Text
2018-08-24 06:47:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1-3. OK
  
 4. FBC A 207, REVISE PLAN TO INDICATE WHICH METHOD OF
 COMPLIANCE IS ELECTED (ACCESSIBLE MEANS OF EGRESS,
 IBC2000 OR IBC2003).
  
 2ND REVIEW, RESPONSE LETTER STATES THAT THIS IS ON
 ALS.1.4, UNABLE TO LOCATE SELECTION. IT APPEARS THAT
 PLAN WAS REVISED TO COMPLY, BUT PLEASE INDICATE
 SELECTION. REVIEW OF ACCESSIBLE MEANS OF EGRESS WILL BE
 DONE AFTER METHOD (IBC2000 OR IBC2003) IS INDICATED.
  
 5. OK
  
 6-7. ALS.0.1, BUILDING TYPE IIA WITH A NOTE THAT PER
 TABLE 601 FOOTNOTE D, 1 HR FIRE RESISTANCE RATING
 SUBSTITUTED BY FIRE SPRINKLER. THIS CAN ONLY BE TAKEN
 IF THE SPRINKLERS ARE NOT REQUIRED BY OTHER PROVISIONS
 OF THE CODE. A STORY INCREASE WAS TAKEN (FROM 3 TO 4),
 SO THIS EXCEPTION CANNOT BE UTILIZED.
  
 8. OK
  
 9. FBC 107.3.5.1.1(5), FBC EB 904, PROVIDE FIRE
 PROTECTION PLANS TO SHOW COMPLIANCE WITH STANDPIPES FBC
 B 905.3.1(1) AND NFPA13 SPRINKLERS FBC B 903.2.11.3.
  
 10. FBC 107.3.5.1.1(6), FBC EB 904, PROVIDE FIRE ALARM
 PLANS TO SHOW COMPLIANCE WITH FBC B 907.2.2.
  
 11. ALS.1.1, FBC 107, NOTE STATES THAT "2014 FBC
 SECTION 1004.4 FIXED SEATING" (CONFERENCE ROOM), IS
 THIS CORRECT? IF THIS IS NOT FIXED SEATING, REVISE NOTE
 AND REVISE OCCUPANT LOAD ACCORDINGLY.
  
 2ND REVIEW, THIS LANGUAGE IS STILL ON THIS PAGE. THIS
 WILL BE REDLINED IF NOT REMOVED. RESPONSE LETTER REFERS
 TO "REVISED ALS1.1" BUT A NEW SHEET WAS NOT PROVIDED.
  
 12. ALS.1.1, PLAN INDICATES SIGNAGE AT STAIR INDICATING
 NO ACCESS. IT DOES NOT APPEAR THAT A SIGN WILL BE
 ADEQUATE TO PREVENT USE OF THE STAIR. ADDITIONAL MEANS
 MAY BE REQUIRED. PRIOR TO C.O. ADDITIONAL INFORMATION
 WILL BE REQUIRED REGARDING HOW OCCUPANTS WILL BE
 PREVENTED FROM ACCESSING THE STAIR. UNLESS YOU WISH TO
 REVISE THE PLAN OR PROPOSE SOMETHING AT THIS TIME, THIS
 WILL BE A PROVISO ITEM.
  
 OR, SEE FBC EB 805.2 EXCEPTION 2.
  
 13. OK
  
 14. ALS.1.2, FBC A 202.4, IT APPEARS THAT A PORTION OF
 THE 2ND FLOOR LACKS VERTICAL ACCESSIBILITY. PROVIDE
 RATIONALE. PLEASE PROVIDE VIA EMAIL PRIOR TO
 RESUBMITTAL.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT THIS WAS
 REVISED, BUT SHEET ALS1.2 WAS NOT REVISED (NOR WAS
 A1.2.1, ALSO OTHER 2ND FLOOR PAGES).
  
 15-16. OK
  
 17. A0.0.2, A WOOD CEILING IS SHOWN. IF THIS IS A TYPE
 I OR TYPE II BUILDING, THIS APPEARS TO BE PROHIBITED,
 SEE FBC B 603 FOR COMBUSTIBLES PERMITTED IN A NON
 COMBUSTIBLE BUILDING.
  
 2ND REVIEW, IT IS NOT CLEAR HOW THIS WAS ADDRESSED.
  
 18-21. OK
  
 22. SEOR TO REVIEW SOILS; INCORPORATE REFERENCE INTO
 PLAN OR PROVIDE A SHOP DRAWING REVIEW STAMP.
  
 23-24. OK
  
 25. ENERGY CALCS, CLARIFY THE FOLLOWING OR REVISE
 ACCORDINGLY:
 A. EXTERNAL LIGHTING IS NONE; HOW WILL THIS BUILDING
 COMPLY WITH MEANS OF EGRESS ILLUMINATION IN THE EXIT
 DISCHARGE? SIGNAGE FOR THE BUILDING? LIGHTS ON THE
 EXTERIOR? SP1.0.1 SHOWS EXTERIOR LIGHTING.
 B. WALLS SHOWN FOR 2ND FLOOR ONLY, WHERE IS THE DATA
 FOR THE OTHERS?
 C. WINDOWS SHOWN ON 2ND FLOOR ONLY, WHERE IS DATA FOR
 THE OTHERS?
 D. NO DOORS SHOWN.
 E. NO DATA FOR ROOF; AREN'T THERE TWO DIFFERENT TYPES
 OF ROOFS ON THIS BUILDING?
 F. FLOORS APPEAR TO SHOW SLAB ON GRADE FOR ALL LEVELS.
  
 2ND REVIEW, NEW ENERGY CALCS WERE NOT PROVIDED.
  
 NEW COMMENT:
  
 26. ALS0.1, OCCUPANCY CALCULATIONS, CLOUD OBSTRUCTS THE
 OCCUPANT LOAD.
  
  
 27. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 A. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES. PRODUCTS TO BE
 SUBMITTED (LIST MAY NOT BE COMPREHENSIVE):
 NANAWALL
 STOREFRONT
 GLAZED DOORS
 OPAQUE DOORS
 OVERHEAD DOORS
  
 WHEN SUBMITTING PRODUCT APPROVALS, PROVIDE A LOCATION
 PLAN.
  
 C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
 ***************************
 INTERNAL USE ONLY:
  
 USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG
 SQUARE FEET - 36706
  
 CONSTRUCTION TYPE: ???
 UNITS:
 FLOORS: 4
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 36706
 SQ FT FOOTPRINT: 36706
 SQ FT ROOF: 36706
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD:
 PROP USE: OFFICE
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED B
  
  