2018-06-05 07:37:19 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| 553.79(5) 2016, THIS IS A THRESHOLD BUILDING (FOUR |
| STORIES). |
| ***NO WORK TO RESUME ON THE STRUCTURE PERMIT UNTIL THE |
| FOLLOWING ITEMS ARE ADDRESSED*** |
| FAILURE TO IMMEDIATELY RESOLVE THESE ISSUES WILL RESULT |
| IN REVOCATION OF THE STRUCTURE PERMIT 17120610 AS THIS |
| PERMIT WAS ISSUED IN ERROR. |
| |
| 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT |
| OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO |
| CONTRACTOR. |
| |
| 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL |
| PROPOSED INSPECTORS. |
| |
| 3. THRESHOLD STATEMENT REQUIRED BY FS553.79(7)(D) - |
| ENGINEER, REVISE THE STATEMENT SO IT IS CLEAR THAT IT |
| IS FOR COMPLIANCE WITH THE STATUTORY REQUIREMENT. |
| SUGGESTED: |
| |
| "PER FS553.79, TO THE BEST OF THE ENGINEER'S KNOWLEDGE, |
| THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY |
| STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633." |
| |
| PER BUILDING OFFICIAL - ALL STRUCTURAL PAGES FOR THE |
| STRUCTURE PERMIT 17120610 ARE TO BE REVISED TO INCLUDE |
| THE STATUTORY STATEMENT. |
| |
| 4. THRESHOLD INSPECTION PLAN REQUIRED BY FS553.79(5)A); |
| S0.03, PLEASE REVISE TITLE OF THIS PAGE SO IT IS CLEAR |
| THAT THIS SERVES AS A THRESHOLD INSPECTION PLAN. |
| |
| |
| |
| |