2018-05-31 17:44:011ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. ALS-1-2 THE PLUMBING FIXTURE COUNT STATES A
 OCCUPANT LOAD OF 90 THE 2ND FLOOR OCCUPANT LOAD IS
 LISTED AT 119 PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 2. SHT. A9-5-1 THE SHOWER IN THE WOMENS APPEARS TO BE A
 ALTERNATE ROLL-IN THE DEPTH OF THE SHOWER IS SHOWN AS
 371/4" THE CODE CALLS OUT FOR A HARD DIMENSION OF 36"
 SHALL COMPLY WITH FBC PL 608.2.3
  
 3. SHT. A9-5-1 PLEASE SHOW DIMENSIONS OF THE SHOWER IN
 THE MENS BATHROOM. PER WPB AMEND TO FBC 107.2.1
  
 4. SHT A9-5-2 SHT. A9-5-2 THE TOILET IN THE BATHROOMS #
 203,205,208 SHALL COMPLY WITH FBC PL 604.2
  
 5. SHT. A9-5-9 THE GRAB BARS FOR THE TOILET IN
 BATHROOMS # 203,205, 208 SHALL COMPLY WITH FBC PL
 604.5.1 AND 604.5.2 , 609.4
  
 6. SHT. A9-5-9 THE SHOWERS IN BATHROOMS # 203,205,208
 SHALL COMPLY WITH FBC PL 608 PLEASE INDICATE ON THE
 PLAN WHICH TYPE OF SHOWER COMPARTMENT THEY ARE DESIGNED
 TO TO MEET AND SHOW ALL DIMENSIONS. PER WPB AMEND TO
 FBC 107.2.1
  
 7. SHT A9-5-9 SHOW COMPLIANCE WITH FBC PL 608.3 THE
 GRAB BARS IN-THE SOWERS FOR BATHROOMS # 203,205,208
  
 8. SHT. P5.1 THE SHOWER IN BATHROOM 203, 208 MEN'S
 BATHROOM IN BASEMENT ARE SHOWING A HORIZONTAL DRY VENT
 AND ARE NOT CODE COMPLIANT ALL DRY VENTS SHALL COMPLY
 WITH FBC PL 905.3, 905.4
  
 9. SHT. P5.1 THE TOILET 203 IS NOT VENTED PROPERLY IT
 SHALL BE VENTED BEFORE CONNECTING TO THE BUILDING
 DRAIN. PER FBC PL 901.2.1
  
 10. SHT. P5.1 WHAT VENTING SYSTEM FROM FBC PL CH. 9 ARE
 THE TOILETS IN THE BASEMENT BATHROOMS DESIGNED TO MEET
 IF IT IS A CIRCUIT VENT IT SHALL HAVE A VENT BETWEEN
 THE TWO MOST UP STREAM FIXTURES AND THE VENT HAS TO BE
 DRY . PER FBC PL 914.2
  
 11. PROVIDE A SITE PLAN THAT SHOWS THE CONNECTION OF
 THE SANITARY AND WATER TO THE CITY SYSTEMS. PER WPB
 AMEND TO FBC 107.2.1
  
 12. THE NEW SANITARY FROM THE UPPER FLOORS CAN NOT
 DISCHARGE TO THE SUMP PIT IN THE BASEMENT IT SHALL
 CONNECT TO THE GRAVITY SYSTEM CONNECTED TO THE CITY
 TAP. PER FBC PL 712.1
  
 13. I UNDERSTAND THAT THE SUMP PUMP WILL BE DONE BY
 OTHER BUT PLEASE PROVIDE THE CAPACITY OF THE SUMP PIT
 AND PUMP AND A BASIC PIPING DETAIL.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711