Plan Review Notes
Plan Review Notes For Permit 18040104
Permit Number 18040104
Review Stop M
Sequence Number 1
Notes
Date Text
2018-05-22 12:04:491ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18040104
 5/22/18
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC AND ENERGY CALCULATIONS ARE NOT
 ELECTRONICALLY SIGNED AND SEALED. PLEASE REFER TO RULE
 61G15-23.005: ENGINEERING PLANS, SPECIFICATIONS.
 REPORTS OR OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED
 AND SEALED IN ACCORDANCE WITH THE PROVISIONS OF SECTION
 471.025 FS, AND RULE 61G15-23.001 FAC MAY BE SIGNED
 ELECTRONICALLY AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSUIBLE CHARGE.
  
 2) ENERGYGAUGE FORM: A) COMPLIANCE DATA FOR AHU'S 5, 6,
 7, & 8 HAS NOT BEEN PROVIDED. B) RTU-1 LISTED AT 93,300
 BTUH IN THE ENERGY COMPLIANCE DATA IS NOT SHOWN IN THE
 AC EQUIPMENT SCHEDULES. C) THE 52820 BTUH COOLING
 CAPACITY FOR VAV-3 SHOWN IN THE CALCS DOES NOT MATCH
 THE CAPACITY SHOWN IN THE EQUIPMENT SPECIFICATIONS ON
 SHEET M7.1.
  
 3) SHEETS ALS.01 & M0.1: THE PLANS SHALL BE DESIGNED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODES SIXTH
 EDITION 2017. PLEASE UPDATE THE CODE DATA, AND THE NOA
 FOR THE ROOF STAND. NOA #13-1017.09 HAS BEEN SUPERSEDED
 BY NOA #15-0902.05.
  
 4) M2.5 & M7.1: RTU-1 IS MISLABLED AS RTU-2 ON THE ROOF
 PLAN. SHOW THE LOCATION OF THE 7.5 TON RTU FOR THE
 BUSINESS LOUNGE.
  
 5) PROVIDE COMPLETE VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES IN ACCORDANCE WITH TABLE 403.3.1.1 FBC
 MC. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR, AND EXHAUST AIR WHERE
 REQUIRED.
  
 6) M0.1 & M2.1: DUCT SMOKE DETECTORS ARE REQUIRED FOR
 THE MMU SUPPLY SYSTEMS PER SECTION 606.2.2 FBC MC.
 PLEASE SEE EXCEPTION 2 WHICH ALLOWS SMOKE DETECTORS TO
 BE PLACED IN THE RETURN AIR PLENUMS.
  
 7) M2.1: THE PLAN APPEARS TO SHOW ONLY 135 CFMS OF
 OUTSIDE AIR FOR ALL THE OCCUPIED SPACES ON THE FLOOR.
 SEE COMMENT #4 ABOVE AND PROVIDE CALCULATIONS.
  
 8) M2.1: PROVIDE A MEANS OF RETURN AIR FOR THE SYSTEM.
  
 9) M2.1:USING THE CORRIDOR FOR MAKEUP AIR FOR THE
 TOILET ROOM EXHAUST SYSTEMS REQUIRES THE CORRIDOR TO BE
 DIRECTLY SUPPLIED WITH OUTDOOR AIR AT A RATE GREATER
 THAN THE RATE OF MAKEUP AIR TAKEN FROM THE CORRIDOR-
 SECTION 601.2 (1) FBC MC.
  
 10) M2.2: SHOW HOW IS AIR BEING RETURNED FOM THE
 CONFERENCE AND OFFICE ROOMS- SECTION 601.6 FBC MC.
  
 11) M2.5: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY
 DUCT OF RTU-1 (RTU-2 ON THE PLAN- SEE COMMENT #4).
  
 12) P2.5: PROVIDE A DETAIL SHOWING HOW THE CONDENSATE
 PIPING WILL BE SUPPORTED ON THE ROOF- TYPE AND SPACING
 OF SUPPORTS
  
 13) PROVIDE TWO COPIES OF NOA #15-0902.05. ACKNOWLEDGED
 THAT COMPLETE STRUCTURAL ENGINEERING FOR INSTALLATION
 OF THE RTU'S WILL BE A DEFERRED SUBMITTAL PER NOTE ON
 M6.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  