2018-05-22 12:04:49 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18040104 |
| 5/22/18 |
| |
| CODES IN EFFECT: |
| FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE AC AND ENERGY CALCULATIONS ARE NOT |
| ELECTRONICALLY SIGNED AND SEALED. PLEASE REFER TO RULE |
| 61G15-23.005: ENGINEERING PLANS, SPECIFICATIONS. |
| REPORTS OR OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED |
| AND SEALED IN ACCORDANCE WITH THE PROVISIONS OF SECTION |
| 471.025 FS, AND RULE 61G15-23.001 FAC MAY BE SIGNED |
| ELECTRONICALLY AS PROVIDED HEREIN BY THE PROFESSIONAL |
| ENGINEER IN RESPONSUIBLE CHARGE. |
| |
| 2) ENERGYGAUGE FORM: A) COMPLIANCE DATA FOR AHU'S 5, 6, |
| 7, & 8 HAS NOT BEEN PROVIDED. B) RTU-1 LISTED AT 93,300 |
| BTUH IN THE ENERGY COMPLIANCE DATA IS NOT SHOWN IN THE |
| AC EQUIPMENT SCHEDULES. C) THE 52820 BTUH COOLING |
| CAPACITY FOR VAV-3 SHOWN IN THE CALCS DOES NOT MATCH |
| THE CAPACITY SHOWN IN THE EQUIPMENT SPECIFICATIONS ON |
| SHEET M7.1. |
| |
| 3) SHEETS ALS.01 & M0.1: THE PLANS SHALL BE DESIGNED IN |
| ACCORDANCE WITH THE FLORIDA BUILDING CODES SIXTH |
| EDITION 2017. PLEASE UPDATE THE CODE DATA, AND THE NOA |
| FOR THE ROOF STAND. NOA #13-1017.09 HAS BEEN SUPERSEDED |
| BY NOA #15-0902.05. |
| |
| 4) M2.5 & M7.1: RTU-1 IS MISLABLED AS RTU-2 ON THE ROOF |
| PLAN. SHOW THE LOCATION OF THE 7.5 TON RTU FOR THE |
| BUSINESS LOUNGE. |
| |
| 5) PROVIDE COMPLETE VENTILATION CALCULATIONS FOR ALL |
| ROOMS AND SPACES IN ACCORDANCE WITH TABLE 403.3.1.1 FBC |
| MC. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| PROVIDED CFMS OF OUTDOOR AIR, AND EXHAUST AIR WHERE |
| REQUIRED. |
| |
| 6) M0.1 & M2.1: DUCT SMOKE DETECTORS ARE REQUIRED FOR |
| THE MMU SUPPLY SYSTEMS PER SECTION 606.2.2 FBC MC. |
| PLEASE SEE EXCEPTION 2 WHICH ALLOWS SMOKE DETECTORS TO |
| BE PLACED IN THE RETURN AIR PLENUMS. |
| |
| 7) M2.1: THE PLAN APPEARS TO SHOW ONLY 135 CFMS OF |
| OUTSIDE AIR FOR ALL THE OCCUPIED SPACES ON THE FLOOR. |
| SEE COMMENT #4 ABOVE AND PROVIDE CALCULATIONS. |
| |
| 8) M2.1: PROVIDE A MEANS OF RETURN AIR FOR THE SYSTEM. |
| |
| 9) M2.1:USING THE CORRIDOR FOR MAKEUP AIR FOR THE |
| TOILET ROOM EXHAUST SYSTEMS REQUIRES THE CORRIDOR TO BE |
| DIRECTLY SUPPLIED WITH OUTDOOR AIR AT A RATE GREATER |
| THAN THE RATE OF MAKEUP AIR TAKEN FROM THE CORRIDOR- |
| SECTION 601.2 (1) FBC MC. |
| |
| 10) M2.2: SHOW HOW IS AIR BEING RETURNED FOM THE |
| CONFERENCE AND OFFICE ROOMS- SECTION 601.6 FBC MC. |
| |
| 11) M2.5: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY |
| DUCT OF RTU-1 (RTU-2 ON THE PLAN- SEE COMMENT #4). |
| |
| 12) P2.5: PROVIDE A DETAIL SHOWING HOW THE CONDENSATE |
| PIPING WILL BE SUPPORTED ON THE ROOF- TYPE AND SPACING |
| OF SUPPORTS |
| |
| 13) PROVIDE TWO COPIES OF NOA #15-0902.05. ACKNOWLEDGED |
| THAT COMPLETE STRUCTURAL ENGINEERING FOR INSTALLATION |
| OF THE RTU'S WILL BE A DEFERRED SUBMITTAL PER NOTE ON |
| M6.1. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |