Plan Review Notes
Plan Review Notes For Permit 18040104
Permit Number 18040104
Review Stop E
Sequence Number 1
Notes
Date Text
2018-05-21 09:43:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL RISER NOTE 7 SHOWS A WIREWAY FOR FUTURE
 TENANTS. THIS WIREWAY SHOULD BE TIED INTO THE GROUNDING
 ELECTRODE SYSTEM. PROVIDE CORRECTION. NEC 250.50,
 250.58
 2. ELECTRICAL RISER NOTE 7 SHOWS A WIREWAY FOR FUTURE
 TENANTS. THE WIREWAY IS SHOWN AS BEING INSTALLED, WHILE
 THE METERS AND DISCONNECTS ARE SHOWN AS FUTURE. THIS
 WIREWAY CANNOT BE INSTALLED WITH ENERGIZED CONDUCTORS
 AND NO OVERCURRENT PROTECTION. PROVIDE CORRECTION. NEC
 230.70
 3. PROVIDE LABELING OF MAINS PER NEC 230.2(E)
 4. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET
 ALS.0.1 AND E0.1 IS NOT THE CURRENT CODE. PROVIDE
 CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE)
 5. SHEET ALS.0.1 INDICATES THAT THE BUILDING IS FULLY
 SPRINKLERED. IS THERE A FIRE PUMP AND CONTROLLER, OR IS
 THIS FED FROM CITY WATER? PLEASE CLARIFY. WPB FBC
 107.2.1
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 8. RESTROOMS ON 3RD FLOOR DO NOT SHOW THE AUTOMATIC
 LIGHTING CONTROL REQUIRED. PROVIDE CORRECTION. FBC EC
 C405.2
 9. SHEET E2.5, THE UNISEX RESTROOM DOES NOT SHOW THE
 AUTOMATIC LIGHTING CONTROL REQUIRED. PROVIDE
 CORRECTION. FBC EC C405.2
 10. PROVIDE NOTE REQUIRING GFCI DEVICE FOR WATER
 COOLERS TO BE READILY ACCESSIBLE. NEC 422.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  