2018-05-21 09:43:02 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ELECTRICAL RISER NOTE 7 SHOWS A WIREWAY FOR FUTURE |
| TENANTS. THIS WIREWAY SHOULD BE TIED INTO THE GROUNDING |
| ELECTRODE SYSTEM. PROVIDE CORRECTION. NEC 250.50, |
| 250.58 |
| 2. ELECTRICAL RISER NOTE 7 SHOWS A WIREWAY FOR FUTURE |
| TENANTS. THE WIREWAY IS SHOWN AS BEING INSTALLED, WHILE |
| THE METERS AND DISCONNECTS ARE SHOWN AS FUTURE. THIS |
| WIREWAY CANNOT BE INSTALLED WITH ENERGIZED CONDUCTORS |
| AND NO OVERCURRENT PROTECTION. PROVIDE CORRECTION. NEC |
| 230.70 |
| 3. PROVIDE LABELING OF MAINS PER NEC 230.2(E) |
| 4. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET |
| ALS.0.1 AND E0.1 IS NOT THE CURRENT CODE. PROVIDE |
| CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE) |
| 5. SHEET ALS.0.1 INDICATES THAT THE BUILDING IS FULLY |
| SPRINKLERED. IS THERE A FIRE PUMP AND CONTROLLER, OR IS |
| THIS FED FROM CITY WATER? PLEASE CLARIFY. WPB FBC |
| 107.2.1 |
| 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| 8. RESTROOMS ON 3RD FLOOR DO NOT SHOW THE AUTOMATIC |
| LIGHTING CONTROL REQUIRED. PROVIDE CORRECTION. FBC EC |
| C405.2 |
| 9. SHEET E2.5, THE UNISEX RESTROOM DOES NOT SHOW THE |
| AUTOMATIC LIGHTING CONTROL REQUIRED. PROVIDE |
| CORRECTION. FBC EC C405.2 |
| 10. PROVIDE NOTE REQUIRING GFCI DEVICE FOR WATER |
| COOLERS TO BE READILY ACCESSIBLE. NEC 422.5 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |