2019-04-09 11:31:00 | PERMIT # 18040097 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| APPROVED WITH COMMENTS: |
| |
| 1) ALL WORK AND REQUIREMENTS SHALL COMPLY WITH THE 6TH |
| EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH |
| CONTAINS THE 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 |
| WITH FLORIDA AMENDMENTS. |
| |
| 2) PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND |
| DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF |
| NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| |
| 3) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION |
| SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? |
| |
| 4) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| SYSTEM AND/OR FIRE ALARM SYSTEM. |
| |
| |