2019-05-10 18:59:32 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-ARCHITECT TO SPECIFY MATERIALS TO BE USED IN FIRE |
| RATED CEILINGS & TENANT SEPARATION WALLS PRIOR TO |
| INSPECTIONS. SEC. 702.6 FBC-EXISTING BUILDING. |
| |
| 2- SIZE OF BEDROOM WINDOWS ON UNITS #5 AND #12 WERE |
| REDUCED. THERE ARE NO PERMITS TO CHANGE THE SIZE OF THE |
| WINDOWS. REVISE WINDOW SIZE TO ORIGINAL SIZE. |
| |
| 3- SEC. 702.4 FBC-EXISTING BUILDING: WINDOW OPENING |
| CONTROL DEVICES COMPLYING WITH ASTM F2090 MAY BE |
| REQUIRED IF IN GROUP R-2 IF ALL OF THE FOLLOWING APPLY |
| TO THE REPLACEMENT WINDOW: (1)THE WINDOW IS OPERABLE; |
| (2)THE WINDOW REPLACEMENT INCLUDES REPLACEMENT OF THE |
| SASH AND THE FRAME; (3)IN GROUP R-2 THE TOP OF THE SILL |
| OF THE WINDOW OPENING IS AT A HEIGHT LESS THAN 36 |
| INCHES (915 MM) ABOVE THE FINISHED FLOOR; (4)THE WINDOW |
| WILL PERMIT OPENINGS THAT WILL ALLOW PASSAGE OF A |
| 4-INCH-DIAMETER (102 MM) SPHERE WHEN THE WINDOW IS IN |
| ITS LARGEST OPENED POSITION; AND (5)THE VERTICAL |
| DISTANCE FROM THE TOP OF THE SILL OF THE WINDOW OPENING |
| TO THE FINISHED GRADE OR OTHER SURFACE BELOW, ON THE |
| EXTERIOR OF THE BUILDING, IS GREATER THAN 72 INCHES |
| (1829 MM). THE WINDOW OPENING CONTROL DEVICE, AFTER |
| OPERATION TO RELEASE THE CONTROL DEVICE ALLOWING THE |
| WINDOW TO FULLY OPEN, SHALL NOT REDUCE THE MINIMUM NET |
| CLEAR OPENING AREA OF THE WINDOW UNIT TO LESS THAN THE |
| AREA REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 4- IF CHANGING FLOORING, THEN PROVIDE THE FOLLOWING: |
| FLOORING SOUND INSULATION MATERIAL: A) COPY OF THE |
| FLAME SPREAD INDEX & SMOKE DEVELOPED INDEX TEST (ASTM E |
| 84 OR UL 723) SEC. 720.1 OF FBC. B) COPY OF THE SOUND |
| TRANSMISSION CLASS (STC) TEST ( ASTM E 90) SEC. 1207.2 |
| OF FBC. AND C) COPY OF THE IMPACT INSULATION CLASS |
| (IIC) TEST (ASTM E 492) SEC. 1207.3 OF FBC 6TH EDITION. |
| |
| |