2018-12-17 17:43:551ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE PLUMBING SHEET WITH DETAILED SCOPE OF WORK
 ESTIMATE FROM M COSTA PLUMBING STATES THE REPLACEMENT
 OF SANITARY STACKS AND REPIPING WATER LINE PROVIDE
 ISOMETRIC DRAWINGS FOR ALL PLUMBING BEING REPLACED. PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. PROVIDE UPDATED SPEC FOR THE WATER HEATERS THE ONES
 THAT WERE PROVIDED WERE FROM 2012 AND DON'T MEET THE
 CURRENT ENERGY CODE SHALL COMPLY WITH FBC ENERGY TABLE
 C404.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  