Plan Review Notes For Permit 18040097 |
Permit Number |
18040097 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-12-17 17:43:55 | 1ST REVIEW: | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. PROVIDE PLUMBING SHEET WITH DETAILED SCOPE OF WORK | | ESTIMATE FROM M COSTA PLUMBING STATES THE REPLACEMENT | | OF SANITARY STACKS AND REPIPING WATER LINE PROVIDE | | ISOMETRIC DRAWINGS FOR ALL PLUMBING BEING REPLACED. PER | | WPB AMEND TO FBC 107.3.5.1.3(13) | | | | 2. PROVIDE UPDATED SPEC FOR THE WATER HEATERS THE ONES | | THAT WERE PROVIDED WERE FROM 2012 AND DON'T MEET THE | | CURRENT ENERGY CODE SHALL COMPLY WITH FBC ENERGY TABLE | | C404.2 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|