2018-12-06 14:10:25 | PLAN DENIED | | 1) 1ST FLOOR HALL AND LAUNDRY ROOM MISSING FIRE DAMPERS | | PER SECTION 602.2.1 FBC (M) 2017 FIRE PARTITIONS | | 2) 2ND FLOOR HALL AND STORAGE ROOM MISSING FIRE DAMPERS | | PER SECTION 602.2.1 FIRE PARTITIONS FBC (M) 2017 | | 3) SHOW LOCATION OF DRYER EXHAUST TERMINATION. SECTION | | 507 CLOTHES DRYER EXHAUST. FBC (M) 2017 | | 4) JUST A REMINDER NO COMBUSTIBLES IN RETURN AIR PLENUM | | INCLUDING DOORS. SECTION 602.2.1 MATERIALS IN PLENUM'S. | | FBC (M) 2017 | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|