Plan Review Notes
Plan Review Notes For Permit 18040097
Permit Number 18040097
Review Stop M
Sequence Number 3
Notes
Date Text
2018-12-06 14:10:25PLAN DENIED
 1) 1ST FLOOR HALL AND LAUNDRY ROOM MISSING FIRE DAMPERS
 PER SECTION 602.2.1 FBC (M) 2017 FIRE PARTITIONS
 2) 2ND FLOOR HALL AND STORAGE ROOM MISSING FIRE DAMPERS
 PER SECTION 602.2.1 FIRE PARTITIONS FBC (M) 2017
 3) SHOW LOCATION OF DRYER EXHAUST TERMINATION. SECTION
 507 CLOTHES DRYER EXHAUST. FBC (M) 2017
 4) JUST A REMINDER NO COMBUSTIBLES IN RETURN AIR PLENUM
 INCLUDING DOORS. SECTION 602.2.1 MATERIALS IN PLENUM'S.
 FBC (M) 2017
  