Plan Review Notes For Permit 18040097 |
Permit Number |
18040097 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-05-17 13:18:27 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. COMPLY WITH BUILDINGS COMMENTS. | | | | 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE WATER | | HEATERS. PER WPB AMEND TO FBC 107.2.1 | | | | 3. PROVIDE BREAKER SIZE FOR WATER HEATER SHALL COMPLY | | WITH MANUFACTURE INSTALLATION GUIDE. PER WPB AMEND TO | | FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|