Plan Review Notes For Permit 18040097 |
Permit Number |
18040097 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-05-09 10:13:28 | PLAN DENIED | | 1) PROVIDE DUCT SIZE, CFM AND GRILL SIZE ON PLANS. | | 2017 FBC (M) | | 2) REFER TO SECTION 601.6 BALANCED RETURN AIR | | 2017 FBC (M) | | 3) REFER TO SECTION 602.2.1 MATERIALS WITH IN | | PLENUM'S. ( NO COMBUSTIBLES ALLOWED IN RETURN AIR | | PLENUM'S INCLUDING DOORS 2017 FBC (M) | | 4) PROVIDE EQUIPMENT SCHEDULE ON PLANS | | 107.3.5.1.4 MINIMUM PLAN REVIEW ( MECHANICAL ) | | 5) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION | | DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. | | 6) PROVIDE ENERGY CALCULATIONS WITH THE PLAN | | SECTION 603.2 DUCT SIZING 2017 FBC (M) | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|