2018-05-09 10:13:28PLAN DENIED
 1) PROVIDE DUCT SIZE, CFM AND GRILL SIZE ON PLANS.
 2017 FBC (M)
 2) REFER TO SECTION 601.6 BALANCED RETURN AIR
 2017 FBC (M)
 3) REFER TO SECTION 602.2.1 MATERIALS WITH IN
 PLENUM'S. ( NO COMBUSTIBLES ALLOWED IN RETURN AIR
 PLENUM'S INCLUDING DOORS 2017 FBC (M)
 4) PROVIDE EQUIPMENT SCHEDULE ON PLANS
 107.3.5.1.4 MINIMUM PLAN REVIEW ( MECHANICAL )
 5) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 6) PROVIDE ENERGY CALCULATIONS WITH THE PLAN
 SECTION 603.2 DUCT SIZING 2017 FBC (M)
  