2018-04-04 14:23:2104/04/2018 1ST GAS REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
  
  
 1) SHOW PIPE SIZE ON OUTLET OF GAS METER. SUBMIT AN
 ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL
 CUT SECTIONS OF PIPE PER 2017 FBC-FUEL GAS, SECS.
 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. G2413.4.1,
 G2413.4.2
  
 2) CITY RECORDS SHOW EXISTING GAS SYSTEM ( POOL HEATER)
 LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21). THE PLANS INDICATE
 AN EXISTING GAS METER. THE BTU LOAD OF THE EXISTING GAS
 SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE
 SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED.
 IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR THE STOVE TO VERIFY COMPLIANCE
 WITH STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS
 CODE SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC.
 G2404.3. GAS APPLIANCES SHALL BE LISTED AND LABELED.
 THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES /
 EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION.
 FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 4) ) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED
 GAS APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL
 GAS SEC.304.9.3 OR FBCR G2407.9.3
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  
  