2018-04-08 09:51:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHOW LOCATION OF EXISTING FPL METER ON PLAN.
 GENERALLY SPEAKING, CONDUCTORS ARE NOT PERMITTED TO
 EXTEND INTO THE DWELLING WITHOUT OVERCURRENT
 PROTECTION, UNLESS IT IS A BACK TO BACK SITUATION OR
 THE CONDUCTOR LENGTH IS MINIMAL. PROVIDE CLARIFICATION
 AND/OR CORRECTION TO INCLUDE A MAIN DISCONNECT ON THE
 EXTERIOR OF THE DWELLING IF NEEDED. NEC 230.70; FBC RE
 E3601.6; FBC 107.2.1
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE LOAD CALCULATION PROVIDED SHOWS THE FIRST
 10,000 VA AS A LOAD OF ONLY 3846.4, INSTEAD OF THE FULL
 10,000 THAT IT IS SUPPOSED TO BE. PROVIDE CORRECTION.
 NEC 220; FBC RE E3602.2
 6. BREAKER FOR POOL PUMP REQUIRED TO BE GFCI PROTECTED.
 PROVIDE CORRECTION. NEC 680.21(C); FBC RE E4203.1.3
 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 8. THE AFCI NOTE PROVIDED DOES NOT INCLUDE ALL AREAS
 REQUIRED BY CODE TO HAVE THIS PROTECTION. PER CODE:
 ?ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED.?
 PROVIDE CORRECTION. NEC 210.12; FBC RE E3902.16
 9. PROVIDE GFCI PROTECTED OUTLET ON THE KITCHEN
 PENINSULA. NEC 210.8, 210.52(C)(3); FBC RE E3901.4.3
 10. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE E3903.3
 11. MASTER CLOSET APPEARS TO HAVE A STANDARD RECESS
 LIGHT. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS". PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
 12. PROVIDE A LUMINAIRE CONTROLLED BY A SWITCH LOCATED
 AT THE REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE
 OUTLET INSTALLED AT OR NEAR THE APPLIANCE LOCATION FOR
 THE AHU IN ATTIC. FBC RE M1305.1.3.1
 13. PANEL SCHEDULE SHOWS # 6 WIRE TO BOTH AHU?S ON A 60
 AMP BREAKER. #6 ROMEX WIRE, WHICH IS TYPICAL IN
 RESIDENTIAL WIRING, IS NOT RATED FOR 60 AMPS. PROVIDE
 CORRECTION. NEC 334.80; FBC RE E3705.4.4
 14. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
 15. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER